Integrated Fire Protection System
Electrical Section - Deluge System - F
IRE
C
YCLE
®
III Release
FM-076A-0-72A
Figure 1 - Field wiring diagrams
FM-061H-0-87A
T
BA
5
6
3
4
MAN
U
A
L
P
UL
L S
T
A
T
IO
NS
Z
O
NE
4
Class A / Style D requires CA2Z module.
NOTES:
End-of-line devices are not required for
Class A / Style D wiring.
1
T
BA
2
3
4
5
6
1
2
3
4
TBB
LINE
NEUTRAL
GROUND
120VAC, 60Hz, 165VA MAX
220VAC, 50Hz, 185VA MAX
CONTROL
PANEL
WIRING OF INPUT POWER SOURCES
Refer to Local Electrical Codes for wiring size.
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
24V
DC RE
S
E
T
T
A
B
L
E
C
NO
NC
C
NO
NC
C
NO
C
NO
AL
AR
M
T
RO
UB
LE
SU
PER
VI
S
O
R
Y
W
A
T
E
R
FL
O
W
MAN
U
A
L
P
UL
L S
T
A
T
IO
NS
Z
ON
E 4
N
AC
1
S
ILE
NCE
A
B
L
E
AL
AR
M
N
AC
2
S
ILE
NCE
A
B
L
E
SU
PER
VI
S
O
R
Y
D
ET
EC
T
ION
Z
ON
E 1
CONTACTS RATED 3A, 30VDC RESISTIVE
1
T
BC
2
3
4
5
SH
IE
L
D
RS485
6
7
8
9
10
11
C
NO
NC
MAI
N
VA
L
V
E
SU
PER
VI
S
O
R
Y
C
NO
NC
S
H
U
T-
O
FF
VAL
VE
SU
PER
VI
S
O
R
Y
Contact provided for connection to
the building's central Fire Alarm Panel.
OPTIONAL
LOS ANGELES OPTION
CHICAGO OPTION
NOTE:
All devices are shown in their normal supervisory state.
NOTES:
Use dry contacts with power limited circuits only.
CONTACTS RATED:
5A, 1/6HP, 125/250VAC
0.5A, 250VDC 0.25A, 250VDC
N.C. HEAT DETECTOR
MANUAL RELEASE
DRY CONTACT
END OF LINE RESISTOR
LEGEND
BELL OR HORN
Control panel AC power source is supervised and non-power limited.
5.1K
V
EOLR
5.1K
V
EOLR
5.1K
V
EOLR
5.1K
V
EOLR
WIRING IN
CLASS B / STYLE Y
WIRING IN
CLASS B / STYLE B
OPTIONAL WIRING IN
CLASS A / STYLE D
120
V
2
4V
D
C
NO
N-
R
ESET
T
A
B
L
E
Power limited (supervised) initiating device circuits
Zones 1 (detection) and 4 (manual release):
Max. loop resistance: 100
Ω
End of line: 5.1K
Ω
, 1/4W
Leave ELR (provided) on all unused circuits.
Refer to the VFR-400 release control panel manual for
device compatibility.
Auxiliary power 24Vdc regulated source
Total current available: 0.2A
Resettable for 4 wires smoke detectors
Power limited (supervised) notification appliance
circuits
Output circuits 1 and 2:
Maximum operating voltage: 27Vdc (ripple: 0.3Vdc)
Maximum usable current per circuit: 1.0A
Total current available (all circuits): 2.5A
End of line: 5.1K
Ω
, 1/4W
Leave ELR (provided) on all unused circuits.
Polarity is reversed in supervisory condition.
Refer to the VFR-400 release control panel manual for
device compatibility