Page 2 of 8
T
OTAL
P
AC
®
3
E
Integrated Fire Protection System
Control Section
FM-076A-0-97A
1.5 Control buttons
SCROLL UP / BUZZER SILENCE and
SCROLL DOWN / BUZZER SILENCE
:
When a trouble or supervisory event occurs, a press of this
button will acknowledge each viewed event and the
appropriate output will silence, as well as the applicable
LED. The applicable
TROUBLE
or
SUPERVISORY
input LED
will change from flashing to steady. The message of the
first line on the display will be terminated with
ACK
for each
acknowledged event input. Once all events in trouble or
supervisory state have been viewed, the panel buzzer will
silence. A subsequent trouble or supervisory event will
resume the panel buzzer. Trouble events are self-
restoring. Supervisory events latch and require a reset to
be cleared.
SIGNAL SILENCE
:
By pressing
SIGNAL SILENCE
button, all silenceable outputs
will de-activate, as well as the applicable LED. A trouble
condition will be created, the
TROUBLE
contact will be
activated and the yellow
ALARM SILENCE
LED will light.
WARNING !
Alarms initiated from a
WATERFLOW
signal
cannot be silenced. The panel must be reset to silence
audible devices.
SYSTEM RESET:
The
RESET
button breaks power to all initiating circuits,
4-wire smoke detectors power and will clear any activated
output circuits. If any alarm, supervisory or trouble still
exists after reset, they will reactivate the control panel.
1.6 Time & date settings
1. Slide the program
switch down to
PROGRAM
position.
2. Press on
FUNCTION
button until the following is
displayed.
SET TIME?
3. Press the
SELECT
button to get to the
MINUTES
sub-
menu.
01/21/2000
MINUTES 02:
58
:04
Use
SELECT
button to increase the minutes, or use
SET
button to decrease minutes.
4. Press the
FUNCTION
button to get to the
HOURS
sub-
menu.
01/21/2000
HOURS
02
:58:04
Use
SELECT
button to increase the hours, or use
SET
button to decrease hours.
5. Press the
FUNCTION
button to get to the
DAY
sub-menu.
DAY
01/
21
/2000
02:58:04
Use
SELECT
button to increase day, or use
SET
button to
decrease day.
6. Press the
FUNCTION
button to get to the
MONTH
sub-
menu.
MONTH
01
/21/2000
02:58:04
Use
SELECT
button to increase month, or use
SET
button
to decrease month.
7. Press the
FUNCTION
button to get to the
YEAR
sub-menu.
YEAR 01/21/
2000
02:58:04
Use
SELECT
button to increase year, or use
SET
button
to decrease year.
8. Slide the program
switch up to
RUN
position.