Page 4 of 8
T
OTAL
P
AC
®
3
F
IRE
C
YCLE
®
III
B
Integrated Fire Protection System
Mechanical Section - Deluge System - F
IRE
C
YCLE
®
III Release
FM-076A-0-52A
1.6 Placing the system back in service after operation
1. Verify that the system has been properly drained.
Verify that all system piping auxiliary drain valves are
CLOSED
.
2. Verify that the main water supply valve
(D1)
is
CLOSED
,
and that the manual emergency release valve
(B10)
is
CLOSED
.
CLOSE
main drain valve
(D3)
.
3.
OPEN
priming valve
(B1)
.
4. Reset the release control panel (see section
E
CONTROLS
). Solenoid valve
(F1)
should
CLOSE
. Flow
from solenoid valve to drain should stop. Verify that the
pressure indicated at the priming pressure gauge
(B11)
is equal to, or greater than the pressure indicated at the
water supply pressure gauge
(B12)
.
5.
OPEN
flow test valve
(B6)
.
PARTIALLY OPEN
main water
supply valve
(D1)
.
Note:
Do not open main water supply valve
(D1)
until
gauge
(B11)
shows stabilized pressure.
6. When full flow develops from the flow test valve
(B6)
,
CLOSE
the flow test valve. Verify there is no flow from
drip check valve
(B7)
when the plunger is pushed.
7.
FULLY OPEN
the main water supply valve
(D1)
.
8. Verify that the alarm test valve
(B5)
is
CLOSED
and that
all other valves are in their "normal" operating position
(see paragraph 2.1
NORMAL CONDITION
of the current
section).
9. Reset the release control panel (see section
E
CONTROLS
).
10. Check and repair all leaks.
11. Notify the local
AUTHORITY HAVING JURISDICTION
, remote
station alarm monitors, and those in the affected area
that the system is back in service.
1.7 Inspections and tests
NOTICE
: The owner is responsible for maintaining the fire
protection system and devices in proper operating
condition.
It is imperative that the system be inspected and tested on
a regular basis in accordance with NFPA-25. Refer to
Inspections and Tests recommended in Viking technical
data describing individual components of the deluge
system used.
The frequency of the inspections may vary due to
contaminated or corrosive water supply or corrosive
atmospheres. For minimum maintenance and inspection
requirements, refer to NFPA-25. In addition, the
AUTHORITY HAVING JURISDICTION
may have additional
maintenance, testing, and inspection requirements that
must be followed.
WARNING !
Any system maintenance that involves placing
a control valve or detection system out of service may
eliminate the fire protection capabilities of that system.
Prior to proceeding any testing, notify all local
AUTHORITIES
HAVING JURISDICTION
. Consideration should be given to
employment of a fire patrol in the affected areas.