Page 2 of 2
ICAF -
Integrated Compressed Air Foam System
Sequence of Operation
FM-06IM-0-83A
Emergency Discharge Shut-Off
Because the ICAF System cannot be turned off by the
operation of a single valve as is the case for a standard
sprinkler system, a manual shut-off function is provided. The
CAF discharge can be manually suspended using the
following sequence of operation:
1. Press and hold the function key F3 labeled: "System
Shut-Off" on the keypad of the ARC-1 panel until its
adjacent red lamp is turned On.
2. Close the system main water supply valve
(B10)
inside
the ICAF cabinet. The red lamp labelled "Discharge
suspended" will turn On.
Note
: Mechanical emergency release valve must be in
normal position prior the CAF discharge shut-off.
IMPORTANT
: After a fire, make sure it is completely
extinguished. If necessary, place a fire patrol in the
zone covered by the system. Foam systems that have
been subjected to fire must be returned to service as
soon as possible. The entire system must be inspected
for damage, and repaired or replaced as necessary.
Warning !
DO NOT CLOSE THE WATER SUPPLY TO
MAKE REPAIRS WITHOUT PLACING A FIRE PATROL
IN THE AREA COVERED BY THE SYSTEM. THE
PATROL SHALL REMAIN THERE UNTIL THE SYSTEM
IS BACK IN OPERATION. Advise local authorities of the
necessary work over the fire protection equipment.
Follow emergency procedures required by codes and the
Authority Having Jurisdiction during system maintenance.
Note
: BEFORE CLOSING A VALVE OR ACTIVATING AN
ALARM, ADVISE THE SECURITY GUARD AND THE
CENTRAL SUPERVISORY STATION. THIS IS TO
AVOID DISPATCHING THE FIRE DEPARTMENT IN
CASE OF A FALSE ALARM.
Inspection Log
The function key F1 labelled "Inspection Log" is used in
conjunction with the ARC-1 Remote Interface software for
PC.
Summary of Contents for ICAF System
Page 1: ...Operation Maintenance Manual FM 0723 0 02 A ...
Page 7: ...OWNER S OPERATION MAINTENANCE MANUAL ICAF Integrated Compressed Air Foam System FM 0723 0 5B ...
Page 27: ...Page 4 of 4 ICAF Integrated Compressed Air Foam System System Trim Section FM 0723 0 10 A ...
Page 41: ...Page 2 of 2 J ICAF Integrated Compressed Air Foam System User Notes FM 0723 0 16D User Notes ...