Page 1 of 6
ICAF -
Integrated Compressed Air Foam System
B
Control Panel Section
FM-0723-0-26B
User Interface
F1
F2
F3
Audibles
Silence
Ground Fault
System
Reset
Partial
Disable
AC Power
Alarm
Supervisory
Trouble
Alpha-Numeric Display
System Status LEDs
and Operation Keys
Menu
Navigation Keys
Function
Keys
System LED
Indicators
Alarm Silence
/ Activate
Release
Acknowledge
Discharge
Enter
Menu / Exit
System
Shut-off
Inspection
Log
Shut-Off Key
Activated
Section visible
through
the door window
Left
Right
Up / Previous
Down / Next
Contrast Adjustment
FM-072C-0-275 A
Log
Activated
Discharge
Suspended
Not Used
1. Normal conditions
- The green lamp identified AC
POWER
is activated in
continuous manner.
- All other lamps are deactivated.
- The alpha-numeric display shows default screen
SYSTEM
NORMAL
.
2. System status lamps
Alarm, Trouble and Supervisory lamps will flash for their
respective events until acknowledged, at which point the
lamp will illuminate steadily. The local alphanumeric display
will provide additional details for every event (refer to screen
details in the text).
-
AC POWER
:
A green lamp that illuminates steadily to
indicate the presence of AC power and flashes when
system is on battery power only.
-
AUDIBLES SILENCE
: A yellow lamp that illuminates steadily
when the
ALARM SILENCE
switch has been depressed after
an alarm. Lamp will begin flashing upon subsequent
alarm.
-
GROUND FAULT
: A yellow lamp that illuminates steadily
during a ground fault condition.
-
PARTIAL DISABLE
: A yellow lamp that illuminates steadily
when any input or output circuit is disabled by the user.
-
RELEASE
: A red lamp that illuminates steadily when
solenoid(s) is (are) activated and release occurs. This
lamp will flash when discharge is stopped (cycling type
systems only).
-
DISCHARGE
: A red lamp that illuminates steadily when
the actual water flow has occurred.
-
ALARM
: Red lamp that flashes when an alarm occurs
and becomes steady after event have been
acknowledged.
-
SUPERVISORY
:
A yellow lamp that flashes upon
activation of a supervisory device (such as a tamper
switch and air pressure switch or sensor) and becomes
steady after event have been acknowledged.
-
TROUBLE
: A yellow lamp that flashes for any trouble
condition and becomes steady after event have been
acknowledged. System internal routines trouble will
activate the trouble signals continuously.
-
OPTION LAMPS
: The three (3) option lamps (adjacent to
F1, F2 & F3) are used for various special functions.
Contrast adjustment:
A small potentiometer is provided
on the circuit board to adjust the LCD contrast level. This
potentiometer (shown above) can be accessed from the
bottom of the LCD module when the cabinet door is open
and adjusted with a small flat screwdriver.
Summary of Contents for ICAF System
Page 1: ...Operation Maintenance Manual FM 0723 0 02 A ...
Page 7: ...OWNER S OPERATION MAINTENANCE MANUAL ICAF Integrated Compressed Air Foam System FM 0723 0 5B ...
Page 27: ...Page 4 of 4 ICAF Integrated Compressed Air Foam System System Trim Section FM 0723 0 10 A ...
Page 41: ...Page 2 of 2 J ICAF Integrated Compressed Air Foam System User Notes FM 0723 0 16D User Notes ...