EQUIPMENT:
FIRE
CLASS
PRECEPT EN
PUBLICATION:
FIRECLASS PREC EN INST
ISSUE No. & DATE:
3 13/09/18
PAGE 29 of 30
17.
Mechanical, Electrical & Environmental Specification
Mechanical
Specification
Precept EN
Panel
Repeater
2/4 zone
8 zone
16 zone
32 zone
2-8 zone
16 zone
32 zone
Size [mm]
Height:
Width:
Depth:
370
325
126
370
325
126
370
325
126
441
400
131
370
325
126
370
325
126
441
400
131
Weight excluding
batteries:
6.65Kg
7.05Kg
7.05Kg
9.35Kg
6.65Kg
6.65Kg
7.6Kg
Mains Input
Specification
Precept EN
Panel
Repeater
2/4 zone
8 zone
16 zone
32 zone
2-8 zone
16 zone
32 zone
Maximum Input
Power:
85W
165W
165W
240W
85W
85W
85W
Protection:
[Warning: Replace
only with identical
type & rating of
BEAB or VDE
approved fuse]
T1A
H250V
[1A anti-
surge]
T3.15A
H250V
[3.15A anti-
surge]
T3.15A
H250V
[3.15A anti-
surge]
T3.15A
H250V
[3.15A anti-
surge]
T1A
H250V
[1A anti-
surge]
T1A
H250V
[
1A anti-
surge]
T1A
H250V
[1A anti-
surge]
Voltage:
230V AC +10%/-15%
Cable requirements:
Minimum of 1mm
2
copper protected by a 5A fuse.
Power Supply
Output
Specification
Precept EN Panel
Repeater
2/4 zone
8 zone
16 zone
32 zone
2-8 zone
16 zone
32 zone
Maximum Short
Term Current
Output
(I max b)
1.5A
3A
3A
5A
1.5A
1.5A
1.5A
Maximum Short
Term Current
Output
(I max b)
1.5A
3A
3A
5A
1.5A
1.5A
1.5A
Minimum Output
Current
(I min)
N/A
(PSU is integrated into the
motherboard)
ZERO
N/A
(PSU is integrated into the
motherboard)
Voltage Output,
Mains On
26.5 - 28.6V (27.3V nominal)
Maximum Current
Output, Mains
Failed
1.5A
3A
3A
5A
1.5A
1.5A
1.5A
Voltage Output,
Mains Failed
[* at full load]
20.0* -
28.6V
20.0* -
28.6V
20.0* -
28.6V
20.0* -
28.6V
N/A
Max Ripple
including switching
spikes[full
load/battery
disconnected]
(mV p-p)
200
200
200
750
200
Output Voltage
adjustment
Factory Set
Output protection:
Electronic current limiting
Common fault
output:
N/A
N/A
N/A
25mA
N/A
N/A
N/A
Mains failed fault
output:
N/A
N/A
N/A
25mA
N/A
N/A
N/A