EQUIPMENT:
FIRE
CLASS
PRECEPT EN
PUBLICATION:
FIRECLASS PREC EN INST
ISSUE No. & DATE:
3 13/09/18
PAGE 23 of 30
INPUTS ARE IN PERMANENT RESET AND
OUTPUTS ARE INHIBITED - THE PANEL
WILL NOT RESPOND TO ANY FIRE ALARM.
15.3
To Restore the Factory Default
Configuration for Zones & Outputs:
Open the panel door and locate the DIL
switches SW1-4 to SW1-8 on the motherboard
[Config Non-latch Zones; Config I.S. Zones;
Config M/S Zones; Config Delay Zones; Config
Delay O/Ps] and move the switch actuator on
each switch to the On position.
o
The Config Enabled LED on the motherboard
will flash.
o
The Panel’s System Fault LED will flash and
the buzzer will operate.
o
Any standing fault or disablement indications
will clear.
o
It will not be possible to enter the Select Mode.
Press the Disable button on the panel’s display.
Return DIL switches 1-4 to 1-8 to the OFF
position.
o
The Config Enabled LED on the motherboard
will clear.
o
The Panel’s System Fault LED will flash and
the buzzer will clear.
o
The factory default configuration [all zones as
latching
fire,
non-delay,
standard
[non-
intrinsically safe] will be restored and the Fire
Routing, Fire Protection and Sounder outputs
will no longer be delayed
15.4
Engineer’s Zone/Output Configuration
Time-out Warning:
This feature is provided to prevent the panel being
left in the Zone/Output Configuration condition.
1 minute after the last button press:
o
The panel buzzer will restart.
o
The Select LED will flash.
o
The System Fault LED will continue flashing.
Press the Select On/Off button to continue with
the configuration process otherwise quit the
configuration process as described in 15.2 step
4.
15.5
Invalid Configuration conditions:
Invalid condition: If 2 or more configuration
switches on the motherboard are in the On
position at the same time:
o
The Config LED on the motherboard will flash.
o
The System Fault and Select LEDs on the
display will flash.
o
The fault relay will operate.
o
The panel buzzer will sound.
o
The Cursor indication will clear.
o
Configuration will be inhibited.
To clear the invalid condition check the zone
and output config switches [1/4, 1/5, 1/6, 1/7,
1/8] on the motherboard and ensure that only
one is selected to ON.
Invalid condition: Selecting any config mode
switch [1/4, 1/5, 1/6, 1/7, 1/8] to the On position
whilst the panel is in the fire condition.
o
The Config LED on the motherboard will flash.
o
The System Fault and Select LEDs on the
display will flash.
o
The panel buzzer will sound.
o
The Cursor indication will clear.
o
Configuration will be inhibited.
To clear the invalid condition, select the config
switch to OFF. Reset the fire alarm condition
before attempting the configuration process
again.
15.6
List of configuration DIL switches and
their functions
SW 1/1 - Inhibit F/P on NLZ
:
Selects Fire Protection relay to operate
or
not to
operate for a fire condition on any zone
configured to non-latched mode.
o
OFF Fire Protection relay operates for a fire
condition on any zone configured to non-
latched mode.
o
ON: Fire Protection relay does not operate for
a fire condition on any zone configured to non-
latched mode.
o
[Not EN54 compliant function].
S/W 1/2 - Delay Alarm Sil & Rst:
o
OFF: Silence and reset available as normal.
o
ON: Prevents alarms being silenced or reset
for a period of 3 minutes after a fire alarm
condition occurs.
[Not EN54 compliant function].
SW 1/3 - Delay On Auto:
o
OFF: Automatically turn off the delay mode
once a day at the set time [the delay mode first
being turned on manually].
o
ON: Automatically turn the delay mode on
once a day and off once a day at the set times.
Requires optional clock module.
SW 1/4 - Config Non-Latch Zones:
o
OFF: Configuration mode disabled.
o
ON: Enables selected zones to be configured
to non-
latching fire mode via the Engineer’s
Select feature.
[Not EN54 compliant function].