background image

EQUIPMENT:

   

FIRE

CLASS 

PRECEPT EN 

 

 

 

 

PUBLICATION:

  

FIRECLASS PREC EN INST

 

 

 

 

 

ISSUE No. & DATE:

 

3      13/09/18

 

PAGE 18 of 30 

o

  Remove  the  circuit  faults,  restoring  the  circuit 

to  the  healthy  condition  and  confirm  that  the 
fault indication clears. 

3.  Zone fire conditions  

o

  Starting  with  the  device  nearest  the  panel, 

operate  each  manual  call  point  and  detection 
device on the zone in turn. 

o

  After operation of each device confirm: 

  The  fire  indication  is  provided  on  the  panel 

on the correct zone. 

  The  fire  alarm  devices  operate  correctly  in 

line with the panel configuration. 

  The  Fire  Routing  and  Fire  protection  outputs 

operate  correctly  in  line  with  the  panel 
configuration. 

o

  Press  the  Silence  Alarms  and  the  Reset 

buttons  after  each  device  test  and  check  the 
alarm  clears  (Manual  Call  Points  must  be 
manually reset before resetting the panel). 

4.  Detector removal operation. 

o

  Remove the 1st detector along the zone cable 

[counting  from  the  panel]  on  zone  1  and 
observe the following: 

  The  appropriate  amber  zone  fault  LED 

illuminates 

  The internal buzzer sounds 

  The fault relay operates 

o

  For non I.S. zone applications: 

  Operate  a  manual  call  point  between  the 

detector that has been removed and the EOL 
capacitor.  Check  that  the  panel  reacts  as 
described above for a fire condition.  

  Refit the detector, reset the manual call point, 

press  the  “Silence  Alarms”  button  and  then 
the  “System  Reset”  button  on  the  panel’s 
display  board  and  check  that  the  control 
panel returns to its normal state. 

  Repeat for all detectors on the zone. 

o

  For I.S. zone applications: 

  Remove  the  1st  detector  in  the  zone  cable 

[counting  from  the  panel]  and  operate  a 
manual  call  point  ensuring  that  the  correct 
fire  alarm  condition  is  raised  on  the  panel 
(assuming  the  installation  complies  with 
BS5839). 

  Continue  to  check  the  operation  of  all  other 

manual call points on the  zone, resetting  the 
manual  call  point  and  silencing/resetting  the 
panel at each stage. 

  Refit  the  detector  and  check  that  the  control 

panel returns to its normal state. 

  Continue  to  test  each  of  the  other  detectors 

in turn, checking on each removal that: 

  The  appropriate  amber  zone  fault  LED 

illuminates 

  The internal buzzer sounds. 

  The fault relay operates. 

5.  Repeat steps 1 to 4, one zone at a time, until all 

the zones are commissioned. 

6.  Any  faults  that  are  found  must  be  traced  and 

rectified before proceeding. 

12.7.3  Class Change Input 

1.  Connect  the  Class  Change  switch  to  the  class 

change input on the motherboard. 

2.  Operate the class change switch and observe: 

i)  The alarms sound for 5 seconds then stop. 

ii)  The  internal  buzzer  on  the  panel 

does  not

 

operate. 

iii)  The  internal  buzzer  on  repeaters 

does  not

 

operate. 

3.  De-activate the class change switch  

12.7.4  Fire and Fault Routing Outputs 

1.  Remove  the  resistor  from  the  Fire  Routing 

output  circuit  terminals  and  connect  the  field 
wiring  to  the  terminals,  observing  correct 
polarity.  Check  that  any  fault  indications  clear 
after a few seconds. 

2.  To operate the output, initiate a fire condition on 

a  zone.  Check  that  the  fire  signal  is  received  at 
the  receiving  station.  Silence  and  reset  the  fire 
alarm panel to clear the output. 

3.  Remove  the  resistor  from  the  Fault  Routing 

output  circuit  terminals  and  connect  the  field 
wiring  to  the  terminals,  observing  correct 
polarity.  Check  that  any  fault  indications  clear 
after a few seconds. 

4.  Initiate a fault condition on the fire alarm panel to 

signal a fault to the remote receiving station. 

5.  Confirm  the  receipt  of  the  fault  warning  at  the 

receiving station. 

6.  Open-circuit  the  output  wiring  of  each  circuit  in 

turn,  Confirm  the  fire  alarm  panel  indicates  Fire 
Routing and Fault Routing faults appropriately. 

7.  Reconnect  the  cabling  and  confirm  the  faults 

clear. 

12.7.5  Fire Protection control signal 

1.  Ensure  any  fire  protection  equipment  to  be 

controlled via the Fire Protection output is locked 
off/safe  before  attempting  any  connection, 
testing or commissioning. 

2.  Remove  the  resistor  from  the  Fire  Protection 

output  circuit  terminal  and  connect  the  field 
wiring  to  the  terminals,  observing  correct 
polarity.  Check  that  any  fault  indications  clear 
after a few seconds. 

3.  Initiate a fire condition on  a  zone to operate the 

output.  Check  that  the  fire  signal  operates  the 

Summary of Contents for Precept EN 16

Page 1: ...PREC EN INST ISSUE No DATE 3 13 09 18 PAGE 1 of 30 Johnson Controls Tyco Fire Security GmbH Victor von Bruns Strasse 21 8212 Neuhausen am Rheinfall Switzerland Precept EN Fire Detection Alarm Panel P...

Page 2: ...15 4 ENGINEER S ZONE OUTPUT CONFIGURATION TIME OUT WARNING 23 15 5 INVALID CONFIGURATION CONDITIONS 23 15 6 LIST OF CONFIGURATION DIL SWITCHES AND THEIR FUNCTIONS 23 15 7 CONFIGURABLE OPTIONS VIA DIL...

Page 3: ...eps that are taken in designing installing and commissioning a FIRECLASS Precept EN system 1 Install all field wiring and equipment Refer to the Installation Guidelines in section 11 2 below Refer to...

Page 4: ...h label C1631 repeater interface optional J18 B Figure 3 Precept EN 32 Zone Internal View TB 1 30 J 1 J 1 TO MOTHERBOARD 25 TB 2 26 27 TB 3 18 17 19 TB 5 28 TB 4 29 TB 6 ZONE CIRCUITS 20 21 22 TB 8 31...

Page 5: ...EQUIPMENT FIRECLASS PRECEPT EN PUBLICATION FIRECLASS PREC EN INST ISSUE No DATE 3 13 09 18 PAGE 5 of 30 Figure 4 2 4 Zone Precept EN panel General Assembly with optional clock module...

Page 6: ...EQUIPMENT FIRECLASS PRECEPT EN PUBLICATION FIRECLASS PREC EN INST ISSUE No DATE 3 13 09 18 PAGE 6 of 30 Figure 5 8 16 Zone Precept EN panel General Assembly with optional clock module...

Page 7: ...EQUIPMENT FIRECLASS PRECEPT EN PUBLICATION FIRECLASS PREC EN INST ISSUE No DATE 3 13 09 18 PAGE 7 of 30 Figure 6 32 Zone Precept EN panel General Assembly with optional clock module...

Page 8: ...nnect to Aux DC 24V 24V DC relay Typical zonal output wiring Field relay spec Coil resistance 2 6K to 4 5K Ohms Voltage 24V DC Nom min 18V max 30V Fitted with suppression diode as shown Relay local to...

Page 9: ...A B GND Reset N C Inputs SIL Silence alarms EVAC Evacuate RST Reset Outputs DIS Disablement active EVAC Evacuation active BUZ Active Buzzer active Class change Buz Active Lower terminal tier Upper te...

Page 10: ...LED indicators OUTPUT OK Battery Charger Fault Charger Fault Mains Fault J18 Earth Fault Monitoring Link Secondary AC from transformer C1631 Repeater Interface Connector for C1632 Zone Expansion Board...

Page 11: ...denoting any one of the following conditions a Battery or associated wiring disconnected b Battery fuse blown c Low Battery voltage 15 7V 0 4V d Battery and interconnection resistance is equal to or...

Page 12: ...ne Panel Power Supply Layout Secondary AC Supply from Transformer 28V 0V DC Power output Mains Fault Output Common Fault Output 4 way header for connector to 32 zone motherboard for DC power common fa...

Page 13: ...care when lifting and transporting batteries For weights above 24 kilos lifting aids should be used DANGER Do NOT attempt to remove the battery lid or tamper with the internal workings of the battery...

Page 14: ...h contain PCBs with sensitive and fragile electronic components on them You must place them in an area that is clean dry and dust free where they will not be damaged You can place them inside the orig...

Page 15: ...igure 10 Figure 12 Fit the connector on the end of the black lead onto the negative black terminal of the left hand battery Fit the connector on the end of the red lead onto the positive red terminal...

Page 16: ...s and field devices to check each circuit and function in turn to ensure correct operation of the entire system In this way any faults may be located quickly and accurately The general procedures are...

Page 17: ...and the battery is OK the panel should be silent displaying only the Power Supply On indication 5 Turn the Access Keyswitch to 1 and press the Test Display button The panel should respond by lighting...

Page 18: ...ue to test each of the other detectors in turn checking on each removal that The appropriate amber zone fault LED illuminates The internal buzzer sounds The fault relay operates 5 Repeat steps 1 to 4...

Page 19: ...At Repeater 1 turn the Access control switch to 1 and press the Evacuate button Check that the alarms operate and the internal buzzer operates on all repeaters 3 Press the Silence button on the fire a...

Page 20: ...ult Disabled Yellow Flashes for a fault on the Fault Routing Output Steady when Fault Routing Output is disabled POWER SUPPLY ON FIRE FIRE ROUTING ACTIVE GENERAL FAULT POWER SUPPLY FAULT SYSTEM FAULT...

Page 21: ...and if silence before reset is configured sounders are silenced Silence Buzzer 1 Press to stop the buzzer sounding in fire or fault conditions Always available 2 In 2 Stage Delay Mode with stage 1 de...

Page 22: ...anel door to allow access to the buttons on the display 2 Select a zone or output to be configured o On the panel display press the Select On Off switch to enable the Select Mode The Select LED will b...

Page 23: ...onfig LED on the motherboard will flash o The System Fault and Select LEDs on the display will flash o The fault relay will operate o The panel buzzer will sound o The Cursor indication will clear o C...

Page 24: ...es Sets the duration of the variable time delay element i e the single stage delay and stage 2 of the two stage delay in steps of 1 minute within the range 0 9 minutes See Table 1 Motherboard Delay Sw...

Page 25: ...ff Off On 5 On Off On Note Address 0 repeater disabled 15 8 Configuring the Fire Routing Fire Protection and Fault routing O Ps To configure the Fire Routing Output to volt free relay contacts remove...

Page 26: ...DISABLE to change MM to desired value 00 to 59 Press SELECT ON Time Set display HH MM SS ON Time SS flashing Press ENABLE or DISABLE to change SS to desired value 00 to 59 To set Day Night Mode Off Ti...

Page 27: ...Settings LINK 1 Position Function Fitted 1st fire alarm time display mode Removed Day Night mode Link 1 DIL Switch 1 DIL Switch Position Function Off 1 Off Clock Module menu configuration disabled 1...

Page 28: ...ulses every second WP DILSW IS ON The backlight remains OFF The panel indicates a general fault and prevents the clock module from being accessed by the user engineer 16 4 2 EEPROM Error Message Data...

Page 29: ...250V 1A anti surge T1A H250V 1A anti surge T1A H250V 1A anti surge Voltage 230V AC 10 15 Cable requirements Minimum of 1mm2 copper protected by a 5A fuse Power Supply Output Specification Precept EN P...

Page 30: ...ff PS1230 2V 3 4Ah 2 off PS1230 12V 3 4Ah Battery size mm L HT H W L 133 W 67 H 60 HT 66 L 151 W 65 H 94 HT 98 L 151 W 98 H 94 HT 100 L 181 W 76 H 167 HT 167 L 133 W 67 H 60 HT 66 L 133 W 67 H 60 HT 6...

Reviews: