![FireClass Precept EN 16 Installation & Commissioning Manual Download Page 26](http://html1.mh-extra.com/html/fireclass/precept-en-16/precept-en-16_installation-and-commissioning-manual_2291350026.webp)
EQUIPMENT:
FIRE
CLASS
PRECEPT EN
PUBLICATION:
FIRECLASS PREC EN INST
ISSUE No. & DATE:
3 13/09/18
PAGE 26 of 30
On the rear of the Clock Module PCB, move the
DIL switch 1, pole 1 on to the ON position.
Pressing ENABLE (+) or DISABLE (-) toggles
setting between
D/N ON
and
D/N OFF
.
To set current time
Press SELECT ↓, to access current Time Set
display:
HH:MM:SS
Time Set
HH flashing
Press ENABLE (+) or DISABLE (-) to change
HH to desired value (00 to 23)
Press SELECT ↓, Time Set display:
HH:MM:SS
Time Set
MM flashing
Press ENABLE (+) or DISABLE (-) to change
MM to desired value (00 to 59)
Press SELECT ↓, Time Set display:
HH:MM:SS
Time Set
SS flashing
Press ENABLE (+) or DISABLE (-) to reset the
SS value to zero.
To set Day/Night Mode On Time
Press SELECT ↓, to access day/night mode ON
Time Set display:
HH:MM:SS
ON Time
HH flashing
Press ENABLE (+) or DISABLE (-) to change
HH to desired value (00 to 23)
Press SELECT ↓, ON Time Set display:
HH:MM:SS
ON Time
MM flashing
Press ENABLE (+) or DISABLE (-) to change
MM to desired value (00 to 59)
Press SELECT ↓, ON Time Set display:
HH:MM:SS
ON Time
SS flashing
Press ENABLE (+) or DISABLE (-) to change SS
to desired value (00 to 59)
To set Day/Night Mode Off Time
Press SELECT ↓, to access day/night OFF Time
Set display:
HH:MM:SS
OFF Time
HH flashing
Press ENABLE (+) or DISABLE (-) to change
HH to desired value (00 to 23)
Press SELECT ↓, OFF Time Set display:
HH:MM:SS
OFF Time
MM flashing
Press ENABLE (+) or DISABLE (-) to change
MM to desired value (00 to 59)
Press SELECT ↓, OFF Time Set display:
HH:MM:SS
OFF Time
SS flashing
Press ENABLE (+) or DISABLE (-) to change SS
to desired value (00 to 59)
Press SELECT ↓, to exit back to Delay On/Off
Set display:
D/N ON
Change?
or
D/N OFF
Change?
Pressing SELECT ↓ repeats the cursor/display
changes as above.
Pressing SELECT ↑ repeats the cursor/display
changes as above in reverse.
To exit Clock Module menu:
Return WP DIL switch on TIMER MODULE to
OFF position.
Press SELECT ON/OFF: Module switches off
the LCD Backlight and exits configuration mode,
Normal Time display:
HH:MM:SS
D/N ON
or
HH:MM:SS
D/N OFF
On completion of editing, return the Access
Control Keyswitch to position 0.