FC410LP SERIES OF LOOP POWERED SOUNDERS AND SOUNDER-BEACONS
INTRODUCTION
The FC410LP Series of Loop Powered Addressable Sounder/ Sounder-Bea-
cons are designed to be driven from an FireClass control panel via the ad-
dressable loop. The FC410LP Series of sounders/sounder beacons consist:
FC410LPSYR
Sounder (indoor use) - red housing
FC410LPSYW
Sounder (indoor use) - white housing
FC410LPSY
Sounder IP65 (outdoor use) - red housing
FC410LPAVR
Sounder-Beacon (indoor use) - red housing
FC410LPAVW
Sounder-Beacon (indoor use) - white housing
FC410LPAV
Sounder-Beacon IP65 (outdoor use) - red housing
The sounder has two volume settings ‘High’ (103 dB ±3) or ‘Low’ (90 dB ±3).
The beacon has two flash rates ‘Slow Flash’ (1/2 Hz) or ‘Fast Flash’ (1 Hz).
The FC410LP devices are synchronised, but not synchronous with other
FireClass sounders (FC430SB/FC410SNM) and beacons (FC430SAB).
The first flash of the beacon is synchronised with the start of the tone.
The FC410LP devices have a built in two port isolator.
TECHNICAL SPECIFICATION
Mechanical Characteristics
Dimensions:
See Fig.
Weight:
Sounder Indoor:
228 g
Sounder Outdoor:
310 g
Sounder-Beacon Indoor:
218 g
Sounder-Beacon Outdoor:
300 g
Materials
Indoor:
ABS FR
Outdoor:
ABS/PC FR
Colour:
White 21-0302
Red 21-0301
Mounting Requirements:
50 mm or 60 mm Besa box or surface mount.
The indoor back box has to two drill positions (on the bottom) for gland holes.
The outdoor back box has 3 drill positions (top and bottom) for gland holes.
The indoor sounder/indoor sounder beacon body clips onto the backbox and
can only be removed by the use of a special key.
The outdoor sounder /outdoor sounder beacon is secured to the backbox by
four allan key screws.
Environmental Characteristics
Temperature:
Indoor
Outdoor
Operating:
-10°C to +55°C
-20°C to +70°C
Storage:
-25°C to +70°C
-25°C to +70°C
Humidity:
Up to 95% RH (non-condensing)
Pressure:
Sounder output is quoted for atmospheric pressure
of 1000mBar.
Vibration:
Meets the requirements of EN 54-3.
Corrosion:
passes the SO
2
corrosion test from EN 54-3.
EMC:
The FC410LP devices comply with the following:
Product family standard EN50130-4 in respect of
Conducted Disturbances, Radiated Immunity, Elec-
trostatic Discharge, Fast Transients and Slow High
Energy.
EN61000-6-3 for Emissions.
IP Rating:
Indoor
Outdoor
IP21C (EN 60529) IP65 (EN54-3 approved to IP33C)
Sound Performance:
high volume
low volume
SPL @ 1m:
103 dB ±3
90 dB ±3
Sound Dispersion
Horizontal:
>90% over 90° (±45° from axis)
Pole Mounted:
>80% over 360° (from axis)
Light Performance:
Flash Power/Light
Output:
2 candela minimum on axis, spacial distribution 60°
@ 1.5 cd
Flash Rate /s:
Fast Flash 1Hz or
Slow Flash
1
/
2
Hz
Synchronisation:
30ms in 30 minutes maximum
Electrical Characteristics
Addressable Loop Voltage:
20 - 40 Vdc
DC Loop Loading
Quiescent:
450 µA
Alarm:
Sounder: Low Volume
3.4 mA
Sounder: High Volume
8.5 mA
S Beacon: Slow Flash + Low Volume
6.5 mA
S Beacon: Fast Flash + Low Volume
7.6 mA
S Beacon: Slow Flash + High Volume
11.1 mA
S Beacon: Fast Flash + High Volume
13 mA
Isolator
Maximum Loop Voltage:
40 Vdc
Minimum Loop Voltage:
19 Vdc
Maximum Rated Continuous Current (Isolator Closed):
2 A
Maximum Rated Switching Current (s/c):
2 A
Maximum Leakage Current (Isolator Open):
6 mA into zone
(10 mA into Isolator)
Maximum Series Impedance (Isolator Closed):
0.25
W
Isolator Switching Threshold (Isolator Closed to Open): 19V or below
Isolator Switching Threshold (Isolator Open to Closed): 3.3V from s/c
Sounder Tones
Table 1 details the tones available for selection in FireClass Console (Future
use expandable to 32 tones).
Approved Tones
The following tones are approved by LPCB to the specifications as shown in
Table 2.
Identification of parts
See Figs 1, 2, 3, 4, 5 and 6.
1
Programming Port
6
Indoor Sounder/Beacon
2
FireClass Control Panel
7
Outdoor Sounder/Beacon
3
801HL Remote Indicator
8
Drill position for glands
4
Indoor Sounder
9
Drill positions for glands top
and bottom
5
Outdoor Sounder
Address Programming
The FC410LP devices have a default factory set address of 255, this must
be set to the loop address of the device using the FC490ST Service Tool.
The sounder is programmed with the address prior to being installed by us-
ing the internal programming port (see Fig. 3).
+
This device use one address only on the loop.
Fixing instructions Doc. version 2.0 16 March 2012