FC410LP SERIES OF LOOP POWERED SOUNDERS AND SOUNDER-BEACONS

INTRODUCTION

The FC410LP Series of Loop Powered Addressable Sounder/ Sounder-Bea-
cons are designed to be driven from an FireClass control panel via the ad-
dressable loop. The FC410LP Series of sounders/sounder beacons consist:

FC410LPSYR

Sounder (indoor use) - red housing

FC410LPSYW

Sounder (indoor use) - white housing

FC410LPSY

Sounder IP65 (outdoor use) - red housing

FC410LPAVR

Sounder-Beacon (indoor use) - red housing

FC410LPAVW

Sounder-Beacon (indoor use) - white housing

FC410LPAV

Sounder-Beacon IP65 (outdoor use) - red housing

The sounder has two volume settings ‘High’ (103 dB ±3) or ‘Low’ (90 dB ±3).
The beacon has two flash rates ‘Slow Flash’ (1/2 Hz) or ‘Fast Flash’ (1 Hz).
The FC410LP devices are synchronised, but not synchronous with other
FireClass sounders (FC430SB/FC410SNM) and beacons (FC430SAB).
The first flash of the beacon is synchronised with the start of the tone.
The FC410LP devices have a built in two port isolator.

TECHNICAL SPECIFICATION

Mechanical Characteristics

Dimensions:

See Fig.

Weight:

Sounder Indoor:

228 g

Sounder Outdoor:

310 g

Sounder-Beacon Indoor:

218 g

Sounder-Beacon Outdoor:

300 g

Materials

Indoor:

ABS FR

Outdoor:

ABS/PC FR

Colour:

White 21-0302
Red 21-0301

Mounting Requirements:

50 mm or 60 mm Besa box or surface mount.

The indoor back box has to two drill positions (on the bottom) for gland holes.
The outdoor back box has 3 drill positions (top and bottom) for gland holes.
The indoor sounder/indoor sounder beacon body clips onto the backbox and
can only be removed by the use of a special key.
The outdoor sounder /outdoor sounder beacon is secured to the backbox by
four allan key screws.

Environmental Characteristics

Temperature:

Indoor

Outdoor

Operating:

-10°C to +55°C

-20°C to +70°C

Storage:

-25°C to +70°C

-25°C to +70°C

Humidity:

Up to 95% RH (non-condensing)

Pressure:

Sounder output is quoted for atmospheric pressure
of 1000mBar.

Vibration:

Meets the requirements of EN 54-3.

Corrosion:

passes the SO

2

corrosion test from EN 54-3.

EMC:

The FC410LP devices comply with the following:
Product family standard EN50130-4 in respect of
Conducted Disturbances, Radiated Immunity, Elec-
trostatic Discharge, Fast Transients and Slow High
Energy.

EN61000-6-3 for Emissions.

IP Rating:

Indoor

Outdoor

IP21C (EN 60529) IP65 (EN54-3 approved to IP33C)

Sound Performance:

high volume

low volume

SPL @ 1m:

103 dB ±3

90 dB ±3

Sound Dispersion

Horizontal:

>90% over 90° (±45° from axis)

Pole Mounted:

>80% over 360° (from axis)

Light Performance:

Flash Power/Light
Output:

2 candela minimum on axis, spacial distribution 60°
@ 1.5 cd

Flash Rate /s:

Fast Flash 1Hz or
Slow Flash

1

/

2

Hz

Synchronisation:

30ms in 30 minutes maximum

Electrical Characteristics

Addressable Loop Voltage:

20 - 40 Vdc

DC Loop Loading

Quiescent:

450 µA

Alarm:

Sounder: Low Volume

3.4 mA

Sounder: High Volume

8.5 mA

S Beacon: Slow Flash + Low Volume

6.5 mA

S Beacon: Fast Flash + Low Volume

7.6 mA

S Beacon: Slow Flash + High Volume

11.1 mA

S Beacon: Fast Flash + High Volume

13 mA

Isolator

Maximum Loop Voltage:

40 Vdc

Minimum Loop Voltage:

19 Vdc

Maximum Rated Continuous Current (Isolator Closed):

2 A

Maximum Rated Switching Current (s/c):

2 A

Maximum Leakage Current (Isolator Open):

6 mA into zone
(10 mA into Isolator)

Maximum Series Impedance (Isolator Closed):

0.25

W

Isolator Switching Threshold (Isolator Closed to Open): 19V or below
Isolator Switching Threshold (Isolator Open to Closed): 3.3V from s/c

Sounder Tones

Table 1 details the tones available for selection in FireClass Console (Future
use expandable to 32 tones).

Approved Tones

The following tones are approved by LPCB to the specifications as shown in
Table 2.

Identification of parts

See Figs 1, 2, 3, 4, 5 and 6.

1

Programming Port

6

Indoor Sounder/Beacon

2

FireClass Control Panel

7

Outdoor Sounder/Beacon

3

801HL Remote Indicator

8

Drill position for glands

4

Indoor Sounder

9

Drill positions for glands top
and bottom

5

Outdoor Sounder

Address Programming

The FC410LP devices have a default factory set address of 255, this must
be set to the loop address of the device using the FC490ST Service Tool.
The sounder is programmed with the address prior to being installed by us-
ing the internal programming port (see Fig. 3).

+

This device use one address only on the loop.

Fixing instructions Doc. version 2.0 16 March 2012

3

FireClass

FC410LP Series of Loop Powered Sounders and Sounder-Beacons

Summary of Contents for FC410LP Series

Page 1: ...st rke 11 1 mA schnelles Blinken und hohe Lautst rke 13 mA TechnischeDaten deseingebauten Isolators max Linienspannung Vmax 40 V min Linienspannung in Ruhe Vmin 19 V max Dauerstrom in durchgeschaltete...

Page 2: ...len schlie en Sie das Sirenenmodul an den Programmieranschluss an siehe Abbildung 3 VERKABELUNG An die Anschlussklemmen k nnen Kabel mit folgenden Drahtquerschnitten angeschlossen werden Litzendraht 0...

Page 3: ...N50130 4 in respect of Conducted Disturbances Radiated Immunity Elec trostatic Discharge Fast Transients and Slow High Energy EN61000 6 3 for Emissions IP Rating Indoor Outdoor IP21C EN 60529 IP65 EN5...

Page 4: ...ng ORDERING INFORMATION FC410LPSYR Sounder indoor use red housing FC410LPSYW Sounder indoor use white housing FC410LPSY Sounder IP65 outdoor use red housing FC410LPAVR Sounder Beacon indoor use red ho...

Page 5: ...ne supera il test di corrosione SO2 della EN 54 3 Compatibilit Elettromagnetica i dispositivi della serie FC410LP sono conformi alle seguenti norme famiglia di prodotto standard EN50130 4 rispetto all...

Page 6: ...llegati come mostrato in figura 5 rispettando la corretta polarit La sezione massima del cavo collegabile ad ogni morsetto di 2 5 mm2 La sezionev calcolatain base alle caratteristiche del cavo e del c...

Page 7: ...menti Thorn Security Ltd Dunhams Lane Letchworth SG6 1BE UK 0832 Installation Instructions 120 515 052 0832 CPD 0571 EN 54 3 2001 A1 2002 EN 54 17 2005 Addressable loop powered Type A sounder for use...

Page 8: ...62 5 0 5 0 110 110 100 Fig 6 Au en und Befestigungsma e Sounder and Sounder Beacon Overall and Fixing Dimensions Sirena e Sirena Lampeggiatore Dimensioni Generali e per il Fissaggio FireClass Via Gab...

Reviews: