background image

P/N: 18122     

Page 4 

Rev. 1.0 

 

Rev Date: 9/7/07 

Wiring the S-2A

  

Connect a length of 16-gauge wire from the control panel positive to the +12 VDC terminal on 
the S-2A display through a 1-amp fuse. Connect a length of 16-gage wire from the control panel 
buss bar ground to the negative terminal on the S2A display.  
 
If you are supplying your own solenoid valve, disconnect solenoid valve from current system and 
wire solenoid valve to S-2A display using figure 6 on page 4.  
 
If you choose to use the valve provided in the carton, which is non-polarized,  wire solenoid valve 
to S-2A display using figure 6  on page 4. 
 
Quick Disconnect Style Sensor with 20’ sensor cable is included. The disconnect/connector plug 
is located 12” from the red sensor. In the event you need to replace the red sensor, simply 
disconnect it at the plug and remove. When reattaching the sensor, make sure the connector 
“snaps” into place by pushing the side locks in. This ensures a watertight seal. No need to reroute 
or replace the 20’ sensor cable. NOTE: If longer sensor length is necessary, contact your retailer 
or our factory for lengths 25’ through 100’.  
 

Sensor Connection  

Plug sensor #1 provided with the S-2A into the connector on the backside of display labeled #1. If 
installing the optional second sensor, plug sensor #2 into the other connector.  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 5 

 
 
 

Summary of Contents for S-2A

Page 1: ...full checking of all operations System operation and correct sensor operation are continually monitored and indicators are provided for fault detection The S 2A has an internal relay for automatic con...

Page 2: ...ower up Unit Fault Off Unit Functional Amber Fault Detected horn beeping Display Installation The S 2A should be mounted in a convenient location preferably at the source of propane usage i e galley h...

Page 3: ...s within nine 9 inches 22 86cm of the ceiling height Do not locate sensor directly over cooking or heating appliances Keep sensor dry Solenoid Installation Propane LPG Mount the solenoid in line on th...

Page 4: ...valve to S 2A display using figure 6 on page 4 Quick Disconnect Style Sensor with 20 sensor cable is included The disconnect connector plug is located 12 from the red sensor In the event you need to r...

Page 5: ...ill vary depending upon usage of the unit Long periods of inactivity will require long warm up periods After the warm up period the indicator will change to green It a sensor is not installed the sens...

Page 6: ...rer for repair Nuisance Alarms The sensor used for the S 2A is sensitive to hydrocarbons an alarm may be triggered by the use of other chemicals such as cleaners paint polish etc The sensors will also...

Page 7: ...as a supplement warning only It is NOT intended to replace standard safety practices which should be carried out around explosive gases i e inspect all rooms and compartments check all gas fittings a...