background image

19

8.2.5 Water filling

1  Check that a water check valve with a shut-off valve (field 

supplied) is connected to the water filling point (water inlet 
connection) for filling the space heating hydraulic circuit 
(see “8.2 Space heating and DHW”).

2  Make sure all the valves are open (water inlet / outlet 

shut-off valves and the rest of valves of the space heating 
installation components).

3  Ensure that the air purgers of the unit and installation are 

open (turn the unit air purger twice at least).

4  Check that the drain pipes connected to the safety valve 

(and to the drain pan in case of installing the “Cooling kit” 
accessory) are correctly connected to the general draining 
system. The safety valve is later used as an air purging device 
during the water filling procedure.

5  Fill the space heating circuit with water until the pressure 

displayed on the manometer reaches approximately 1.8 bar.

 NOTE

While the system is being filled with water, it is highly 
recommended to operate the safety valve manually so as 
to help with the air purging procedure.

6  Remove as much air from inside the water circuit as possible 

through the air purger and other air vents in the installation 
(fan coils, radiators...).

7  Start the air purge procedure test. There are two modes 

(Manual or Automatic) which helps in case of installations with 
heating and DHW operation:

  a.  Manual: start and stop the unit manually using the unit 

controller (run / stop button) and also using the DSW4pin 2 
of the PCB1 (ON: Forced to derive to DHW coil; OFF: Forced 
to derive to space heating).

  b.  Automatic: select the air purge function using the user 

controller. When the automatic air purge function is 
running, the pump speed and the position of the 3-way 
valve (space heating or DHW) are automatically changed:

8  If a little quantity of air is still remaining in the water circuit, 

it will be removed by the automatic air purger of the unit 
during the first hours of operation. Once the air in the 
installation has been removed, a reduction of water pressure 
in the circuit is very likely to occur. Therefore, additional 
water should be filled until water pressure returns to an 
approximate level of 1.8 bar.

 NOTE

•  The unit is equipped with an automatic air purger (factory 

supplied) at the highest location of the unit. Anyway, if 
there are higher points in the water installation, air might 
be trapped inside water pipes, which could cause system 
malfunction. In that case, additional air purgers (field 
supplied) should be installed to ensure no air enters into the 
water circuit. The air vents should be located at points which 
are easily accessible for servicing.

•  The water pressure indicated on the unit manometer may 

vary depending on the water temperature (the higher 
temperature, the higher pressure). Nevertheless, it must 
remain above 1 bar in order to prevent air from entering 
the circuit.

•  Fill in the circuit with tap water. The water in the heating 

installation must comply with EN directive 98/83 EC. 
Non-sanitary controlled water is not recommended 
(for example, water from wells, rivers, lakes, etc.).

•  The maximum water pressure is 3 bar (nominal opening 

pressure of the safety valve). Provide adequate reduction 
pressure device in the water circuit to ensure that the 
maximum pressure is NOT exceeded.

•  For heating floor system, air should be purged by means 

of an external pump and an open circuit to prevent the 
formation of air pockets.

•  Check carefully for leaks in the water circuit, connections 

and circuit elements.

Summary of Contents for Enviroair 11kW

Page 1: ...SUPERIOR HEATING SOLUTIONS SINCE 1980 Installation Operation Manual...

Page 2: ...Firebird Installation Operation Manual 2...

Page 3: ...re Operation 8 5 General Dimensions 9 6 Unit Installation 12 7 Refrigerant and Water Piping 14 8 Drain Piping 15 9 Electrical and Control Settings 22 10 Commissioning 29 11 Unit Controller 31 12 Wirel...

Page 4: ...sional installer according to the applicable regulations Please contact the relevant authorities for more information Models Codification Following Regulation EU No 517 2014 on Certain Fluorinated Gre...

Page 5: ...V 50Hz Unit Enviroair 7 5kW Enviroair 11kW Enviroair 14kW Enviroair 16kW Enviroair Air to Water Heat Pump Models NOTE Icons between brackets mean possible extra operations to the factory supplied oper...

Page 6: ...ducing them into products subsequently sold This document may therefore have been subject to amendments during the life of the product During normal heat pump system design work or unit installation g...

Page 7: ...Device This heat pump is equipped with a high pressure vessel under PED Pressure Equipment Directive The pressure vessel has been designed and tested before shipment according to PED Also in order to...

Page 8: ...em by your service contractor Enviroair 7 5kW Enviroair 11 16kW Turn OFF the main switch when the system is to be stopped for a long period of time If the main switch is not turned OFF electricity wil...

Page 9: ...9 5 General Dimensions Enviroair 11 16kW Enviroair 7 5kW 5 1 Service Space...

Page 10: ...x1 20 Switch for DHW emergency operation 6 Expansion valve x2 21 Sensor for refrigerant pressure 7 Reversing valve 22 Pressure switch for control Pd 8 Solenoid valve 23 Ambient thermistor 9 Accumulat...

Page 11: ...ergency operation 6 Expansion valve x2 21 Sensor for refrigerant pressure 7 Reversing valve 22 Pressure switch for control Pd 8 Solenoid valve 23 Ambient thermistor 9 Accumulator 24 Evaporating temper...

Page 12: ...en cleaning agent is heated Install the unit in a location where noise emitted by the unit does not disturb neighbours Cleaning liquid shall be collected after cleaning Pay attention not to clamp cabl...

Page 13: ...frame width for stable installation as shown in below figure Recommended metal plate size Field supplied material hot rolled mild steel Plate SPHC plate thickness 4 5 T 6 2 Place Provision Concrete fo...

Page 14: ...blast of wind or in an earthquake Calculate quake resistance strength to ensure that installation is strong enough against falling Fix the unit with wires field supplied when installing in a location...

Page 15: ...cuit It is advisable to insulate the water pipes joints and connections in order to avoid heat loss and dew condensation on the surface of the pipes or accidental injures due to excessive heat on pipi...

Page 16: ...filling the unit The check valve acts as a safety device to protect the installation against back pressure back flow and back syphon of non potable water into drinking water supply net 8 2 2 Additiona...

Page 17: ...ing Draining the unit The check valve acts as a safety device to protect the installation against back pressure back flow and back syphon of non potable water into drinking water supply network NOTE T...

Page 18: ...ation take into consideration the following points The storage capacity of the tank has to meet with the daily consumption in order to avoid stagnation of water Fresh water must circulate inside the D...

Page 19: ...urge function is running the pump speed and the position of the 3 way valve space heating or DHW are automatically changed 8 If a little quantity of air is still remaining in the water circuit it will...

Page 20: ...the two following items QI Heat demand from the installation kW While defrosting is taking place the unit is not providing the heat required to cover the heat demand from the installation This value...

Page 21: ...g chlorine mg CI I Less than 0 3 Less than 0 3 Floating carbonic acid mg CO2 I Less than 4 0 Less than 4 0 Index of stability 6 8 8 0 NOTE 1 The mark in the table means the factor concerned with the t...

Page 22: ...W tank heater 0 17 Enviroair 11kW 3N 400V 50Hz With DHW tank heater 0 31 Enviroair 14kW With DHW tank heater 0 31 Enviroair 16kW With DHW tank heater 0 30 NOTE The data corresponding to DHW tank heate...

Page 23: ...in contact with the refrigerant pipes water pipes edges of plates and electrical components inside the unit to prevent damage which may cause electric shock or short circuit CAUTION Use a dedicated po...

Page 24: ...2 x 10 0 mm2 GND 50 2 63 30 Enviroair 16kW 31 2 x 6 0 mm2 GND 32 2 40 30 With DHW tank heater 43 2 x 10 0 mm2 GND 50 2 63 30 Enviroair 11kW 3N 400V 50Hz 14 4 x 4 0 mm2 GND 20 4 40 30 With DHW tank he...

Page 25: ...14 Input 1 Demand ON OFF The air to water heat pump system has been designed to allow the connection of a remote thermostat to effectively control your home s temperature Depending on the room temper...

Page 26: ...ming pool This output will be ON when swimming pool is activated 36 L Output 2 Water pump 3 WP3 When there is a hydraulic separator or buffer tank additional water pump WP3 is needed 37 Output 3 Auxil...

Page 27: ...might occur if changed CAUTION Before setting dip switches first turn the power supply OFF and then set the position of dip switches If the switches are set without turning the power supply OFF the c...

Page 28: ...for circuits 1 and 2 Outdoor unit sensor for circuit 1 Auxiliary sensor for circuit 2 Auxiliary sensor for circuit 1 Outdoor unit sensor for circuit 2 Auxiliary sensor instead of outdoor unit sensor...

Page 29: ...this document and check that the components comply with national and local standards Do not touch any electrical components for more than three minutes after turning OFF the main switch Check the dip...

Page 30: ...e heated gradually Additional optional function can be used for starting at low water temperature conditions Screed drying function The screed function is used exclusively for the process of drying a...

Page 31: ...s a heater or a boiler installed disable the operation before running the test run After Test Run or Air Purge option is selected the Enviroair user controller asks for the duration of the test In cas...

Page 32: ...and a throughput icon indicating the percentage of the actual temperature with respect to the setting temperature It can also show the operation of the electrical heater of the DHW the timer activatio...

Page 33: ...ve view Icon Name Values Explanation Pump This icon informs about pump operation There are three available pumps on the system Each one is numbered and its corresponding number is displayed below to t...

Page 34: ...Controller Wizard Set Up The wizard set up has to be done from the main controller Select language required Press OK Press OK to use configuration assistant Wizard Use arrow keys to set correct time...

Page 35: ...ws to select Radiators Fan Coils or Underfloor Repeat step above if you have a second circuit Press OK If you have two different temperature circuits i e Radiators and Underfloor Heating select 2 If y...

Page 36: ...if Bivalent System Press OK If selected Yes set the Bivalent point for the boiler to be enabled Recommended setting is 5 C Press OK Select No if no swimming pool heating required Press OK Select No if...

Page 37: ...Firebird thermostats are installed select 0 Press OK You will then move to the last screen If Firebird thermostats are installed Select how many 1 or 2 Press OK Use arrows to select wired or wireless...

Page 38: ...nu is active the spanner symbol will appear Menu Button Return Button Home Screen Then press OK Password will then appear on the screen Press Password correct will then appear Below is a guide to navi...

Page 39: ...1 Press right arrow change from Disabled to Two3 Activate Buffer Pump after Buffer Press Menu System Configuration OK Optional Functions OK System OK Hydraulic Separator Status change to enabled Acti...

Page 40: ...individual days and press OK on each day Select accept OK To Set ECO Offset Value Press Menu System Configuration OK Space Heating OK Circuit 1 OK ECO Offset change value to suit DHW Timer Push right...

Page 41: ...ff OK Change Status to Enabled Choose the temperature you want to unit to stop default is 22 C DHW Secondary Circulation Press Menu System Configuration OK Optional Functions OK DHW OK Circuit Pump ch...

Page 42: ...s as means of transmission are prohibited refer to local standards in effect Do not install the gateway close to devices that may be affected by radio waves Do not install the gateway where persons we...

Page 43: ...m 123 x 115 x 37 Weight g 214g Class 2 reinforced insulation device Overvoltage category Class 2 Pollution category Class 2 Operating Temperature 0 C to 60 C Operating Humidity between 30 and 80 Equip...

Page 44: ...Positioned about 1 2m 1 5m from the floor 4 Mount directly to the wall The plugs and mounting screws required are supplied 5 Remove the protective tab between the batteries 6 Attach the thermostat to...

Page 45: ...er to the thermostat If the thermostat screen appears blank after initial installation then check whether the protective film has been removed from the batteries Otherwise try replacing the batteries...

Page 46: ...g touch the left touch zone briefly When the minimum temperature limit is flashing touch the left touch zone again The symbol appears on the screen Touch and hold the left touch zone for 10s and the d...

Page 47: ...om thermostat NOTE Binding can be cancelled from the binding screen by touching and holding on the left touch zone for approximately 10 seconds 9 If binding is unsuccessful then the LED will stay on I...

Page 48: ...ecreased Alternatively when the temperature becomes lower limitation is cancelled Model Enviroair 7 5kW Enviroair 11 16kW For compressor Pressure switches Automatic reset non adjustable each one for e...

Page 49: ...the heat pump capacity will be insufficient to provide demand during extreme climatic conditions This parameter is called the Bivalent Point and is set on the heat pump controller during first commiss...

Page 50: ...r Circuit A ASHP Controller B DHW Thermistor C Cct Thermistor D Switch Live from Htg Cct E Immersion Element F DHW CH 3 Way Vv G Cyl Limit S W H Cyl G3 Vv I Boiler ASHP 3 Way Vv A ASHP Controller B DH...

Page 51: ...er Zone Vv A ASHP Controller B Cct Thermistor D Switch Live from underfloor E Boiler Zone Vv I Boiler Zone Vv 14 8 Suggested Hydraulic Layout with Radiator Circuit when DHW Supplied by a Combi Boiler...

Page 52: ...anomaly THMdhwt Loose disconnected broken or short circuited connector 17 0 Indoor Auxiliary sensor 2 thermistor anomaly THMaux2 Loose disconnected broken or short circuited connector 18 0 Indoor Aux...

Page 53: ...S transmission error if no H LINK RCS has no power No H link communication for a continuous period of 1 minute between Indoor and Unit controller User control by connection wiring breaking wiring erro...

Page 54: ...Firebird Installation Operation Manual 54 Notes...

Page 55: ...55...

Page 56: ...5309 E info firebird ie www firebird ie This brochure was correct at the time of going to print However Firebird s policy is one of continuous development The right is reserved to change specification...

Reviews: