12
EN
The Pulse output will switch back the relay contacts
to their original state after 5 seconds. The Continuous
output will continue to send a signal for as long as the
Alarm sounds.
DIPSWITCH RELAY OPERATION
(ACTIVATION)
Dipswitch 1=on
N/A
Dipswitch 2=on
Buzzer enabled
Dipswitch 3=off
Dipswitch 4=off
Relay A latching continuously
Relay B latching continuously
Dipswitch 3=on
Dipswitch 4=off
Relay A latching for 5 seconds
Relay B latching continuously
Dipswitch 3=off
Dipswitch 4=on
Relay A latching continuously
Relay B latching for 5 seconds
Dipswitch 3=on
Dipswitch 4=on
Relay A latching for 5 seconds
Relay B latching for 5 seconds
Dipswitch 5=on
Battery activated
PLEASE NOTE: When connecting to both output relay
contacts (A & B), it is advisable to install products
(to be switched upon activation of alarm) of the
same power type and not mix between high and low
voltages. This is because the resulting higher voltage
may exceed the defined SELV safe level.
IEC voltage
range
AC RMS
voltage (V)
DC voltage
(V)
Defining
risk
Low voltage 50 to 300
120 to 300
Electrical
shock
Extra-low
voltage
< 50
< 120
Low risk
TESTING
Both contacts should be tested by the installer at the
point of installation to ensure correct operation. The
WRLYB-1 incorporates a separate test button function
(as indicated). Pressing the test button will activate
both relay contacts accordingly.
Please note due to the unique nature of the network,
pressing the test button on a smoke, heat or CO alarm