Model
FS10-CS
TM
Fire Detector with Card Controller
OPTION 2FLCS
INSTALLATION GUIDE and OPERATING MANUAL
Fire Sentry Corporation
Document No. 1527-002
– Rev. E
©
Copyright 2009
All Rights Reserved
Page 14
Rotary Switch #2:
SW
#2
ALERT
Sensitivity (feet)
Fault Code
Notes
0
15
1
30
Factory setting
2
Not Used
5
Invalid setting
3
Not Used
5
Invalid setting
4
Not Used
5
Invalid setting
5
Not Used
5
Invalid setting
6
Not Used
5
Invalid setting
7
ALERT / FEW
Disabled
Notes:
1) Detector Switch #3 is not used.
2) If Detector switch #1 is set for position 0,1,2,3, or 4, a Fault condition #5 will occur. If
Detector switch #2 is set for position 2, 3, 4, 5, or 6, a Fault condition #5 will occur.
2.6
FS10-CS Card Controller, Option 2FLCS, DIP Switch #1 Settings
Use a small flathead screwdriver to set the DIP switch located at the front of the Card
Controller enclosure: ON is UP position.
SW #1
Switched ON
ALARM Timeout (seconds)
Notes
NONE
1
All Positions OFF
1
1
Position 1 ON only
2
2
Position 2 ON only
3
3
Position 3 ON only
4
4
Position 4 ON only
5
5
Factory setting
6
5
Position 6 ON only
7
5
Position 7 ON only
8
5
Position 8 ON only
SECTION 3: OPERATION
3.1 FS10-CS Detector Operation with the Card Controller
The Card Controller does NOT have an ON/OFF switch - the System turns ON when the external
24 VDC Power is applied.