Appendix C: Programming Reference Sheets
--- To enter Programming, press Mode: 7 7 6 4, Enter
❑
00
❑
01
❑
02
❑
03
❑
04
❑
05
❑
06
❑
07
❑
08
❑
09
❑
10
❑
11
❑
12
❑
13
❑
14
❑
15
Addresses 00 to 15 store the Primary Phone Number. Enter 'F' to represent the end of the number.
❑
16
Primary Comm Format:
Enter 0 - F.
❑
17
❑
18
❑
19
❑
20
Primary Account Code: Valid keys are 0-F.
❑
21
❑
22
❑
23
❑
24
Primary 24-Hour Test Time.
Enter military time (i.e. 1400 for 2 PM).
❑
25
Primary Number Test Time Interval. Enter '0' for 24-hour; '1' - 12-hour.
❑
26
❑
27
❑
28
❑
29
❑
30
❑
31
❑
32
❑
33
❑
34
❑
35
❑
36
❑
37
❑
38
❑
39
❑
40
❑
41
Addresses 26-41 store the Secondary Phone Number.
Enter 'F' to represent the end of the number.
❑
42
Secondary Comm Format: Enter 0-F.
❑
43
❑
44
❑
45
❑
46
Secondary Account Code: Valid keys are 0-F.
❑
47
❑
48
❑
49
❑
50
Secondary 24-Hour Test Time.
Enter military time (i.e. 1400 for 2 PM).
❑
51
Secondary Number Test Time Interval. Enter '0' for 24-hour; '1' - 12-hour.
❑
52
❑
53
Start Monitoring Address.
❑
54
❑
55
End Monitoring Address.
❑
56
UDACT-F Communication Selection. Enter '0' to disable UDACT-F communication; '1' for zone report-
ing receive only communication; '2' for zone reporting receive/transmit communication; '3' for point
reporting receive only communication; '4' for point reporting receive/transmit communication; '5' for code
wheel matching point reporting, receive only; or '6' for code wheel matching point reporting, receive/
transmit.
❑
57
Backup Reporting. Enter '0' to have secondary phone number act as backup only; '1' to have secondary
phone number receive all reports and messages along with primary phone number.
❑
58
Touchtone/Rotary Select. Enter '0' for touchtone dialing; '1' for rotary dialing.
❑
59
Make/Break Ratio. If rotary dialing is selected in Address 58; Enter '0' for a 67/73 make/break ratio; '1'
for a 62/38 make/break ratio.
❑
60
Leave default of 0.
❑
61
Leave default of 0.
❑
62
AC Loss Reporting Delay. Enter '0' for no time delay after AC loss; '1' for 6 hour delay; '2' for 7 hour
delay; '3' for 8 hour delay; '4' for 9 hour delay; '5' for 10 hour delay; '6' for 11 hour delay; '7' for 15 hour
delay; '8' for 16 hour delay; '9' for 17 hour delay; 'A' for 18 hour delay; 'B' for 19 hour delay; 'C' for 20
hour delay; 'D' for 21 hour delay; 'E' for 22 hour delay; or 'F' for 23 hour delay.
❑
63
Host Panel ID. Enter '0' for MS-9200; or '2' for SENSISCAN 2000; all other entries are invalid.
❑
64
❑
65
Loop Number for General Reports. Factory set to '00'.
❑
66
❑
67
❑
68
Sensor Number for General Reports. Factory set to '000'.