Power-limited and nonpower-limited circuit wiring must remain separated in the
cabinet. All power-limited circuit wiring must remain at least 0.25" away from any
nonpower-limited circuit wiring. Furthermore, all power-limited circuit wiring and
nonpower-limited circuit wiring must enter and exit the cabinet through different
knockouts and/or conduits. A typical wiring diagram for the UDACT-F is shown
below.
2.3 UL Power-
limited Wiring
Requirements
Figure 2-7: Typical Wiring Diagram for UL Power-limited Requirements
Use power-
limited source
Power-limited circuits