Master Programming Level
Programming
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
53
Output Circuit MAP
Output Mapping (per input zone) allows the programmer/operator to assign the Output Circuits
that will be activated when a particular Input Zone or cross-zoned releasing group goes active.
Pressing
3
for
Output Circuit Map
while viewing Edit Input Zone Screen #2 will display
screens which show the Output Circuits programmed to activate when the selected Input Zone
(or cross-zoned releasing group) is activated. Output Map Screen #1 displays the Output Type
Codes and programming for Output Circuits 1 through 3 and Output Map Screen #2 displays
the Output Type Code and programming for Output Circuit 4.
As an example, if Template 6 has been selected as the FACP Configuration [refer to "FACP
CONFIG (Application Templates)" on page 50], selecting the Output Circuit Map for Input
Zone 1 will display the following screens:
The screens indicate that when Input Zone 1 is activated:
Output Circuit #1 default programmed as
Alarm NAC
will activate (Yes)
Output Circuit #2 default programmed as
Waterflow NAC
will not activate (No)
Output Circuit #3 default programmed as
Release 1
will activate (Yes)
Output Circuit #4 default programmed as
Supv Bell NAC
is not mapped (N/A)
Note that the MAP may indicate that an Input Zone is programmed to a particular Output
Circuit but, if it is cross-zoned with one or more other Input Zones, all must be active in order to
activate the Output Circuit. Refer to the examples in "Circuit Mapping and Cross-Zoning" on
page 103.
The Output Circuit Map can be customized by selecting or deselecting any of the four output
circuits for activation. Pressing the number key corresponding to the selected output will toggle
the display between
Yes
for activation by the Input Zone to
No
for no activation. The new
customized programming is automatically saved by the panel as soon as it is entered.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the
detector currently being programmed. Pressing
1
while viewing Edit Input Zone Screen #3 will
cause the following screen to be displayed:
INPUT ZONE #
1=ENABLED
2=TYPE
3=OUTPUT CIRCUIT MAP
Edit Input Zone Screen #2
OUTPUT MAP ZONE 1
1=ALARM NAC YES
2=WATERFLOW NAC NO
3=RELEASE 1 YES
Output Map Screen#1
OUTPUT MAP ZONE 1
4=SUPV BELL NAC N/A
Output Zone Screen#2
INPUT ZONE #
1=NOUN/ADJECTIVE
2=DESCRIPTION
*****************
Edit Input Zone Screen #3
1=STANDARD ADJECTIVE
2=STANDARD NOUN
Noun/Adjective Screen
Summary of Contents for MRP-2001
Page 8: ...Notes 8 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Page 126: ...Testing Maintenance Maintenance 126 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Page 132: ...Testing Maintenance Maintenance 132 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Page 133: ...Maintenance Testing Maintenance MRP 2001 MRP 2001E PN 53040 A 4 16 2007 133 ...
Page 134: ...Testing Maintenance Maintenance 134 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...