Template 13: Single Hazard - Dual Zone
FACP Configuration Templates
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
115
B.7 Template 13: Single Hazard - Dual Zone
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit).
Input Zone Types:
•
Zone 1 = 2-wire smoke
•
Zone 2 = Fire
•
Zone 3 = Low Pressure
•
Zone 4 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
•
Zone 5 = Pull Station
•
Zone 6 = Manual Release
Output Circuit Types:
•
Output 1 = Alarm NAC
•
Output 2 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
•
Output 3 = Release Solenoid 1 (unsupervised for shorts)
•
Output 4 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
Timers
•
Soak Timer 1 - set for 10 minutes
•
Soak Timer 2 - set for 10 minutes
•
Waterflow Delay Timer - set for 10 seconds
•
AC Loss Delay Timer - set for 2 hours
Operation
•
Activation of Input Zone 1 (2-Wire Smoke)
or
Zone 2 (Fire)
or
Zone 5 (Pull Station)
or
Zone 6 (Manual Release) will operate the Alarm NAC Output #1 and Release Solenoid 1
Output #3. Release Solenoid will turn off water release following time-out of the 10 minute
Soak Timer 1
•
Activation of Input Zone 4 (Waterflow) will operate the Alarm NAC Output #1, Waterflow
NAC Output #2 and Waterflow NAC Output #4. There is a 10 second FACP initiated delay
in activation of these outputs since the Waterflow Delay Timer is set to 10 seconds
•
Activation of Input Zone 3 (Low Pressure) will not operate any Output Circuits (see Relays)
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
•
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull
Station) will operate Alarm Relay
•
Trouble Relay - any system trouble will activate the Trouble Relay
•
Supervisory - activation of Zone 3 (Low Pressure) will operate the Supervisory Relay
TEMPLATE 13: SINGLE HAZARD - DUAL ZONE
INPUT ZONES
1
2
3
4
5
6
OUTPUT CIRCUITS
2-WIRE SMOKE
FIRE
LOW
PRESS.
WATERFLOW
PULL
STATION
MANUAL
RELEASE
#1 ALARM NAC
X
X
X
X
X
#2 WATERFLOW NAC
X
#3 RELEASE SOLENOID 1
X
X
X
X
#4 WATERFLOW NAC
X
Summary of Contents for MRP-2001
Page 8: ...Notes 8 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Page 126: ...Testing Maintenance Maintenance 126 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Page 132: ...Testing Maintenance Maintenance 132 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...
Page 133: ...Maintenance Testing Maintenance MRP 2001 MRP 2001E PN 53040 A 4 16 2007 133 ...
Page 134: ...Testing Maintenance Maintenance 134 MRP 2001 MRP 2001E PN 53040 A 4 16 2007 ...