ENGINEERING SPECIFICATIONS

Smoke detector shall be an ionization type (Model 1400)

as manufactured by System Sensor.  Wiring connections

shall be made by means of SEMS screws.  Detector will

have a visible LED which will blink in standby and latch on

in alarm.  The detector shall have a sensitivity of 1.9 ±

0.6%/ft. as measured in the UL smoke box.  The detector

screen and cover should be easily removable for clean-

ing.  It shall be possible to perform a sensitivity and func-

tional test on the detector without the need of generating

smoke.  The detector shall have a mounting bracket that

allows for mounting to a 3-1/2" (8.89 cm) or 4" (10.16 cm)

octagonal box or a 4" (10.16) square electrical box.

SPECIFICATIONS, Model 1400

Type:

  Ionization.

Visual LED local alarm:

  Yes.

Remote LED annunciator capability:

  Yes.

Operating voltage range:

  8.5 - 35 VDC.

Current limits:

a) Standby (max.):  100 µA @ 24 V.
b) Alarm current (typical):  

See Note 1.

c) Alarm current (max.):  

See Note 1.

Maximum ripple voltage:

 4 V peak-to-peak.

Reset voltage:

  2.5 VDC.

Reset time: 

 0.3 seconds.

Startup time:

  2 seconds.

Size:

  3.12" (7.9 cm) high, 5.5" (13.9 cm) diameter.

Air velocity rating:

  1,200 feet per minute (7.6 meters per

second) maximum.

Weight:

 0.7 lbs. (317.5 grams).

Mounting:

  4" (10.16 cm) square box (1.5" [3.81 cm] min.

depth) with plaster ring; 3.5" (8.89 cm) or 4" (10.16 cm)

octagonal box; 50, 60 or 75 mm boxes.

Operating temperature:

  32°F to 120°F (0°C to 49°C).

Operating humidity:

  10% to 93% relative humidity, (non-

condensing).

Latching alarm:

  Reset by momentary power interruption.

Test features:

   

Test port:

  Insert 0.1" (2.54 mm) maxi-

mum diameter allen wrench or screwdriver into test port

on detector housing.  

Test module:

  Using a standard

voltmeter interface, insert MOD400R plug into detector's

module port.  Fulfills calibrated sensitivity test per NFPA

72.

NOTE 1:

  Two-wire control panels must limit current to 100 mA

or less.

PRODUCT INFORMATION

Model

Description

1400

Ionization Smoke Detector, 2 wire, Surface

Mount.

RA400Z

Remote Annunciator (LED).

MOD400R

Field test module for all of the System Sen-

sor 400 Series smoke detectors.

1400 WIRING DIAGRAM

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com