Page 2 of 2 DF-50484
ENGINEERING SPECIFICATIONS
Smoke detector shall be an ionization type (Model 1400)
as manufactured by System Sensor. Wiring connections
shall be made by means of SEMS screws. Detector will
have a visible LED which will blink in standby and latch on
in alarm. The detector shall have a sensitivity of 1.9 ±
0.6%/ft. as measured in the UL smoke box. The detector
screen and cover should be easily removable for clean-
ing. It shall be possible to perform a sensitivity and func-
tional test on the detector without the need of generating
smoke. The detector shall have a mounting bracket that
allows for mounting to a 3-1/2" (8.89 cm) or 4" (10.16 cm)
octagonal box or a 4" (10.16) square electrical box.
SPECIFICATIONS, Model 1400
Type:
Ionization.
Visual LED local alarm:
Yes.
Remote LED annunciator capability:
Yes.
Operating voltage range:
8.5 - 35 VDC.
Current limits:
a) Standby (max.): 100 µA @ 24 V.
b) Alarm current (typical):
See Note 1.
c) Alarm current (max.):
See Note 1.
Maximum ripple voltage:
4 V peak-to-peak.
Reset voltage:
2.5 VDC.
Reset time:
0.3 seconds.
Startup time:
2 seconds.
Size:
3.12" (7.9 cm) high, 5.5" (13.9 cm) diameter.
Air velocity rating:
1,200 feet per minute (7.6 meters per
second) maximum.
Weight:
0.7 lbs. (317.5 grams).
Mounting:
4" (10.16 cm) square box (1.5" [3.81 cm] min.
depth) with plaster ring; 3.5" (8.89 cm) or 4" (10.16 cm)
octagonal box; 50, 60 or 75 mm boxes.
Operating temperature:
32°F to 120°F (0°C to 49°C).
Operating humidity:
10% to 93% relative humidity, (non-
condensing).
Latching alarm:
Reset by momentary power interruption.
Test features:
Test port:
Insert 0.1" (2.54 mm) maxi-
mum diameter allen wrench or screwdriver into test port
on detector housing.
Test module:
Using a standard
voltmeter interface, insert MOD400R plug into detector's
module port. Fulfills calibrated sensitivity test per NFPA
72.
NOTE 1:
Two-wire control panels must limit current to 100 mA
or less.
PRODUCT INFORMATION
Model
Description
1400
Ionization Smoke Detector, 2 wire, Surface
Mount.
RA400Z
Remote Annunciator (LED).
MOD400R
Field test module for all of the System Sen-
sor 400 Series smoke detectors.