5
6. Choice of installation location
6.1 Environmental checks
• See characteristics and technical data paragraph to check the required environmental conditions (protection
rating, temperature, humidity, altitude, etc.)
• The installation location shall be easily accessible
• Prevent access to the installation location by children
• Installation of the unit in a location exposed to solar rays makes the warranty void as it may cause:
- power limitation phenomena in the battery unit
- premature wear of the electrical/electromechanical components
- premature wear of the mechanical components (gaskets)
- reduction in performance, lifetime and possible damage of the battery unit
• Do not install in small closed rooms where air cannot circulate freely
• Always ensure that the flow of air around the battery unit is not blocked so as to prevent overheating.
• Do not install in locations where flammable substances or gases may be present
• Do not install on wooden walls or near flammable substances.
• Do not install in locations with a constant presence of water and/or high humidity level.
• Do not install in rooms where people live or where the prolonged presence of people or animals is expected,
because of the noise that the system produces during operation The level of the sound emission is heavily
influenced by where the appliance is installed (for example: the type of surface around the inverter, the general
properties of the room, etc.) and the quality of the electricity supply.
• Respect the minimum distances from objects around the battery unit that could prevent the inverter installation
and restrict or block the air flow.
• The installation must take account of any electrical devices (e.g. lamps, switches, etc.) which must be at least
20cm from the equipment. These distances must be maintained also to facilitate the circulation of the air
needed to cool the unit and to facilitate the operations to install/maintain hardware and software which is done
by dismantling the covers placed on the front.
• Install vertically with a maximum inclination of 5° (forward or backward).
• Avoid electromagnetic interference that can compromise the correct operation of electronic equipment, with
the consequent hazards
• Install on a wall or strong structure suitable to bear the weight
• Install at a height which takes into consideration the weight of the appliance and in a position which is suitable
for servicing, unless suitable means are provided to carry out the operation
• The ambient temperature of the installation location should be between 5°C and 30°C to guarantee the optimal
operation of the battery unit (REACT2-BATT). Here below are the functions available from the system on the
basis of the ambient temperature:
T1 - Optimal operation of the REACT2 system
T2 - Correct operation of the REACT2 system with possible reduction of power
T3 - Operation limited to the inverter part only. Management of the battery is disabled.
-20
-10
0
+5
+30
+40
+55
T1
T2
T3
°C
T2
T3
ATTENTION –
A
Final installation of the battery unit must not compromise access to any externally located disconnection devices.
20cm
10cm
20cm
10cm
20cm
10cm
20cm
10cm
20cm
10cm
20cm
10cm
REACT2 system
REACT2-UNO
REACT2-BATT
60
cm
60
cm
60cm
60cm
BATT
BATT
20cm
10cm
20cm
10cm
20cm
10cm
20cm
10cm
20cm
10cm
20cm
10cm
REACT2 system
REACT2-UNO
REACT2-BATT