3.  List of supplied components

Available components for REACT2-BATT

Qty

Bracket for REACT2-BATT wall 

mounting

1

Cable lug for earth cable

2

REACT2-BATT power 

connection cable

1

REACT2-BATT signal 

connection cable

1

 

M5 hex nuts , M5 flat washer 

and M5 serrated lock washer 

for protective earth cable 

installation

1+1+1

Technical documentation

1

4.  Safety precautions

Battery System provides a safe source of electrical energy when operated 

as intended and as designed.

Potentially hazardous circumstances such as excessive heat or electrolyte 

mist may occur under improper operating conditions, damage, misuse 

and/or abuse. The following safety precautions and the warning messages 

described in this Part must be observed. 

 ATTENTION – 

A

HIGH VOLTAGE – ELECTRIC SHOCK HAZARD. 

Do NOT open any cover of REACT2-BATT

4.1  Organic Solvent Electrolyte

Cell components of Battery System contain organic solvent-based 

electrolyte. Breach of individual cells may allow some electrolyte to be 

released from the cell. Direct contact with the liquid electrolyte can cause 

skin irritation. 

If contact with the liquid electrolyte occurs, follow the suggestions below to 

minimize the chance of injury: 

• Flush eyes immediately with cold running water for at least 15 minutes. 

• Rinse skin immediately with water for at least 15 minutes. 

• Remove clothing if soiled. 

• Seek immediate medical attention.

4.2  Electrolyte Vent Product

Organic solvent electrolyte vent products are flammable. To avoid of 

flammable products, the following guidelines must be observed:

•  Operate the Battery System under conditions only as specified

•  Keep sparks, flames and smoking materials away from the Battery

•  Do not incinerate, puncture or impact the Battery System.

•  Do not solder or weld to the Battery System.

 ATTENTION – 

A

HAZARD. The hazard warnings (set out below) are 

used to indicate risks or unsafe practices that CAN cause serious 

injury or death.

•  DO NOT dismantle or disassemble any parts.

•  DO NOT set light to or heat.

•  DO NOT use or leave near a naked flame, boiler or heated places 

(beyond the temperature range indicated in the technical data). 

•  DO NOT wet with fresh or salt water. 

•  DO NOT create damaging impacts or drop.

•  DO NOT use for other equipment. 

•  DO NOT touch directly if there is a leak of electrolyte material. 

•  DO NOT touch if it shows any breaks in the cover where any parts under 

voltage are visible.

•  DO NOT use should a fault or any anomaly (such as in smell, heat, 

colour, smoke, shape or noise) be found.

 WARNING – 

B

The warnings (set out below) are used to indicate risks 

or dangerous actions which COULD cause serious personal harm or 

damage to the product or property.

•  Do not use with other inverter models if not expressly indicated by 

FIMER. 

•  Do not use if is leaking of electrolyte material.

•  Do not use if anomalies are present. Should the battery unit have a bad 

smell, changes in colouring, deformation or other anomalous conditions 

during use (including charging and storage), do not use it.

 ATTENTION – 

A

CAUTION. The caution messages (set out below) 

are used to indicate risks or dangerous actions which could cause 

serious harm to people or damage to property.

•  Do not use or leave exposed to direct sunlight (or in a vehicle which is 

exposed to the sun). The REACT2-BATT could produce heat, smoke, 

breakages or flames. In addition, its performance might deteriorate and/

or it might have a shorter lifespan.

 ATTENTION – 

A

Final installation of the equipment must not hinder 

access to any externally located disconnection devices.

Summary of Contents for REACT2-BATT

Page 1: ...he safety and installation information provided in the product manual must be read and followed The technical documentation for the product is available at the website The device must be used in the manner described in the manual If this is not the case the safety devices guaranteed by the inverter might be ineffective ...

Page 2: ... 5 6 A Vdc operating range 170 575 V Out of 0 to 40 C 32 to 104 F temperature range power derating occurs PROTECTIVE CLASS I Made in Italy A B A Inverter battery model B Main technical data ATTENTION A The labels attached to the equipment must NOT be removed damaged dirtied hidden etc In the manual and or in some cases on the equipment the danger or attention zones are indicated by signs labels sy...

Page 3: ...way from the Battery Do not incinerate puncture or impact the Battery System Do not solder or weld to the Battery System ATTENTION A HAZARD The hazard warnings set out below are used to indicate risks or unsafe practices that CAN cause serious injury or death DO NOT dismantle or disassemble any parts DO NOT set light to or heat DO NOT use or leave near a naked flame boiler or heated places beyond ...

Page 4: ...country concerned In addition to the regulations in force in the Country of interest the following recommendations should be followed Store the Battery Unit in its original packing including the pallet in a dry cool well ventilated environment and away from water Do not open tamper with the original packing Do not crush deform the packing Equip the storage environment with appropriate PPE Never le...

Page 5: ...d the battery unit that could prevent the inverter installation and restrict or block the air flow The installation must take account of any electrical devices e g lamps switches etc which must be at least 20cm from the equipment These distances must be maintained also to facilitate the circulation of the air needed to cool the unit and to facilitate the operations to install maintain hardware and...

Page 6: ...l the required 2 holes B to mount the bracket Install the REACT2 BATT bracket 20 to the support 01 20 B B 2 xØ 9 mm STEP 1 STEP 2 Lift the REACT2 BATT up to the bracket and insert the heads of two anchor points present on the back of the battery unit into the slots on the bracket 20 LIFTING U Risk of injury due to the heavy weight of the equipment Hang up the lower part of the REACT2 BATT to the w...

Page 7: ...o anchor points present on the back of the battery unit into the slots on the bracket 20 LIFTING U Risk of injury due to the heavy weight of the equipment Hang up the lower part of the REACT2 BATT to the wall using the two wall attachment point 26 holes diameter 11 mm 21 02 20 B B 2 xØ 9 mm STEP 1 STEP 2 Remove the caps from the battery units connectors if present To remove the battery signal conn...

Page 8: ...nge battery will be disabled Suggested ambient temperature 5 30 C Storage temperature 20 25 C 6 months or 20 45 C 3 months Relative humidity 4 100 condensing Physical Cooling Natural Dimension H x W x D 740 mm x 490 mm x 229 mm Weight 50 kg Mounting system Wall bracket Safety Protective class I Marking CE Safety IEC 62619 UN38 3 UN3480 For more information please contact your local FIMER represent...

Reviews: