MAXIMUM NUMBER OF CONVENTIONAL DEVICES PER ZONE MUST NOT EXCEED 20 DEVICES. 
CONVENTIONAL ZONES ARE Z5 to Z8 ONLY 

Conventional Device Zones: Z5 - Z8: 

 

26-1509  Issue 2 

Known to be compatible with 
 

Apollo 55000-317 Series 65 optical smoke detector 
Hochiki SLR-E3N Conventional Photoelectric Smoke Detector 
Nittan EVC-P Photoelectrical Optical Smoke Detector 
System Sensor 2020P Conventional Optical Smoke  

 

+    + 

-     - 

+    + 

-     - 

+    + 

-     - 

Z5 + 
Z5 - 

SCRN 

+    + 

-     - 

 

MANUAL 

CALL 

POINT 

SMOKE 

OR HEAT 

DETECTOR 

SMOKE 

OR HEAT 

DETECTOR 

SMOKE 

OR HEAT 

DETECTOR 

MANUAL 

CALL 

POINT 

EOL 

END OF LINE 

DIODE 

DO NOT SPUR 

(wiring not monitored) 

 
Detector bases with integral continuity diodes must be used to ensure manual call points remain operational 
when a detector head is removed from its base. 
 
Manual call points with integral resistors must be used to prevent a short circuit fault occurring instead of a 
fire condition when activated. 
 
An EOL diode provided with the expanstion card must be connected across the terminals of the last device 
on each circuit to allow the wiring to be monitored. 
 
The wiring for each detector circuit should be connected to the relevant connector block on the Main Control 
PCB and their screens terminated at the panel 
 
For more specific device wiring information, please refer to the manufacturers’ own instructions. 
 
If a conventional zone is 

NOT 

used it 

MUST 

be switched off using the zone status menu in the engineers 

programming options or an EOL diode provided with the expanstion card must be connected across the 
connector block on the Main Control PCB as shown below   
 
 

Z5 + 
Z5 - 

SCRN 