Programming
151086
5-7
21
Dialer
Menu
AC LOSS HOURS
Enter the number of hours before AC power loss is
reported. Set to 6-12 hours for NFPA 72 Fire Alarm
Systems for Central Station Service (Chapter 4-3). Set
to 15 hours for NFPA 72 Remote Supervising Station
Fire Alarm Systems (Chapter 4-5). Set to 0 if you are
using a Cheetah control panel.
To program a number larger than 9, use:
for 10
for 11
for 12
for 13
for 14
for 15
_______
Default = 6
22
Dialer
Menu
# RINGS
Enter the number of rings before 10-2256 answers a
downloading call. Options are 2-14, minimum is 2.
Enter "0" to disable ring detector.
____
Default = 10
NOTES FOR STEPS 23 THROUGH 27.
Steps 23-27 apply only if the 3/1 format is selected. The 3/1 format is an old format that does not make full use of 10-2256 reporting
capabilities. The 3/1 format sends only one digit or letter for an event. It does not send the zone number with the event. Use this
format only if required by the receiver.
If you are using the 3/1 reporting format, use Steps 23-27 to select the digit (0-9) that will be sent for each event.
The letters A through E can be used if the receiver can accept them. Use
for A,
for B and so on.
Do not duplicate any digits or letters. For example, do not use "0" for both alarm code (in Step 23) and trouble code (in Step 25).
Note that the 3/1 format does not distinguish between "0" and "A", so do not use "0" if you're using "A" and vice versa.
See Section 6 for more information about the 3/1 format.
23
Dialer
Menu
3/1 ALARM CODE
Select the digit that will be transmitted to the central
station for an alarm.
(See "NOTES" above if you need more information.)
____
Default = 1
24
Dialer
Menu
3/1 SPRKLR CODE
(Feature available with revision H or
later boards.)
3/1 code for sprinkler supervisory conditions.
(See "NOTES" above if you need more information.)
____
Default = 2
25
Dialer
Menu
3/1 TROUBLE CODE
3/1 code for trouble conditions.
(See "NOTES" above if you need more information.)
____
Default = 8
Table 5-1: Programming Form
Step # /
06-151
Menu
Option
Description
Your choice (D) =
Default
SHIFT 1
SHIFT 2
SHIFT 3
SHIFT 4
SHIFT 5
SHIFT 6
SHIFT 1
SHIFT 2
OBSOLETE
Summary of Contents for 10-2256
Page 8: ...Model 10 2256 Fire Slave Communicator Installation Manual 1 4 151086 O B S O L E T E ...
Page 24: ...Model 10 2256 Fire Slave Communicator Installation Manual 3 14 151086 O B S O L E T E ...
Page 28: ...Model 10 2256 Fire Slave Communicator Installation Manual 4 4 151086 O B S O L E T E ...
Page 44: ...Model 10 2256 Fire Slave Communicator Installation Manual 6 6 151086 O B S O L E T E ...