Programming
151086
5-5
NOTES FOR STEPS 7-10:
Channel response time speeds are not intended to be used as a smoke verification feature. Possible choices for channel response
times are 0-3 (described below).
7
System
Menu
ZONE RESPONSE #1
0 = 0.3 to 0.4 seconds
1 = 3 to 4 seconds
2 = 15 to 20 seconds
3 = 30 to 40 seconds
Note:
If you make a mistake and program a
number other than 0-3, the resulting zone speed
will be:
4 = 0.3 to 0.4 seconds
5 = 3 to 4 seconds
6 = 15 to 20 seconds
7 = 30 to 40 seconds
8 = 0.3 to 0.4 seconds
9 = 3 to 4 seconds
r
0.3 to 0.4 sec (D)
r
3 to 4 sec
r
15 to 20 sec
r
30 to 40 sec
8
System
Menu
ZONE RESPONSE #2
Factory programmed as "1" (3 to 4 seconds). Cannot
be changed.
No selection.
9
System
Menu
ZONE RESPONSE #3
(See step 6.)
r
0.3 to 0.4 sec (D)
r
3 to 4 sec
r
15 to 20 sec
r
30 to 40 sec
10
System
Menu
ZONE RESPONSE #4
(See step 6.)
r
0.3 to 0.4 sec (D)
r
3 to 4 sec
r
15 to 20 sec
r
30 to 40 sec
11
System
Menu
RELAY #1
0 = Relay activates on alarm
1 = Relay activates on system trouble
r
Alarm
r
Trouble (D)
12
System
Menu
INSTALLER'S CODE
Installer's code [4 digits]. For programming and other
system control functions. Can also perform all the
same operations as the operator's code. (See Section
4.2 for specific information about which functions the
code can perform.)
________________
Default = 5128
Table 5-1: Programming Form
Step # /
06-151
Menu
Option
Description
Your choice (D) =
Default
OBSOLETE
Summary of Contents for 10-2256
Page 8: ...Model 10 2256 Fire Slave Communicator Installation Manual 1 4 151086 O B S O L E T E ...
Page 24: ...Model 10 2256 Fire Slave Communicator Installation Manual 3 14 151086 O B S O L E T E ...
Page 28: ...Model 10 2256 Fire Slave Communicator Installation Manual 4 4 151086 O B S O L E T E ...
Page 44: ...Model 10 2256 Fire Slave Communicator Installation Manual 6 6 151086 O B S O L E T E ...
Page 48: ...Model 10 2256 Fire Slave Communicator Installation Manual 7 4 151086 O B S O L E T E ...