Model 10-2256 Fire Slave Communicator Installation Manual
3-4
151086
3.2.3
Wiring and Board Layout Diagram
Figure 3-1 Model 10-2256 Wiring and Board Layout
3.2.4
Electrical Ratings
PRIMARY DC:
VDC: 18 - 40
Current draw, standby at 24 VDC
143 mA max. with annunciator attached 84 mA max. without annunciator
Current draw, alarm at 24 VDC
227 mA max. with annunciator attached 154 mA max. without annunciator
AC RATING:
45 mA max.
CHANNEL (ZONE) INPUTS:
0 - 30 VDC input 10 mA max. current draw
MAX. WATCHDOG RESPONSE:
50 seconds