OMMUNICATION
M
APPING
• • • • • •
EtherNet/IP to FifeNet Data
In each of the three configurations (single- dual- or triple-drive CDP-01), the EtherNet/IP to FifeNet
data is the same. The table below shows the configuration mapping for data traveling from
EtherNet/IP to FifeNet. The control matrix data on data word 1 is present so that if it is mapped to the
parallel input for the CDP-01, a great deal of control can be exercised without a special state machine
in the CDP-01. If this control is insufficient, the data capabilities on Data Words 2 through 6 are
provided for custom application using state machine interpretation.
Table 4-1
ETHERNET / IP TO FIFENET DATA – SINGLE-, DUAL-, OR TRIPLE-DRIVE CDP-01
CDP-01 Matrix
100246-02X Single
100247-02X Dual
100248-02X Triple
SBPC-21-EN/IP Matrix
100410-02X Single
100411-02X Dual
100412-02X Triple
Word
1
Data
Type
2
Variable
Description
0 (0x00)
WORD
Device 1
Command
3
Network commands sent to the CDP-01. Simulated key presses, etc.
1 (0x01)
WORD
Control Matrix
Used to control the CDP-01 in accordance with the control matrix.
2 (0x02)
WORD
[0] Reserved
These values are reserved for state machine communication.
3 (0x03)
WORD
[1] Reserved
4 (0x04)
WORD
[2] Reserved
5 (0x05)
INT
[3] Reserved
6 (0x06)
INT
[4] Reserved
1
All data words are 16-bit.
2
Data Types:
INT 16-bit signed value in the range of –32,768 to +32,767.
WORD 16-bit unsigned value in the range of 0 to 65,535.