Field Controls HHSC+ User Manual Download Page 9

page 9

EXAMPLE: MEETING ASHRAE 62.2 2010 with given conditions:

•  2000 square foot home (conditioned space) with 3 bedrooms
•  140 cfm of fresh air flow as measured in the fresh air duct while system is operating

SETTING THE VENTILATION % TO MEET VENTILATION CODES:

1. 

Determine the required constant ventilation flow rate from table: 50 cfm.

2. 

Measure the actual flow rate through the fresh air duct using a flow hood, anemometer, or Pitot tube 
and manometer, with the HVAC fan running on lowest speed and the FAD damper open (temporarily 
jumper AUX-IN to R terminal, or activate remote override device if connected): Example: 140 cfm 
measured.

3. 

Calculate the Ventilation %:  Divide the constant flow rate from the table by the actual fresh air flow rate 
measured and multiply by 100%: 

Ventilation % = 50 ÷ 140 x 100% = 36% (rounding up)

For this example, setting the Ventilation % at 36% will ensure ventilation meeting ASHRAE 62.2, regardless 
of any other settings, as long as the HHSC+ system is set to on, and the inhibit feature is not active.  Setting 
Ventilation % to a higher value will raise the ventilation above the minimum as required by ASHRAE 62.2
To meet other ventilation codes, substitute the alternately required constant ventilation rate in cfm from step 
1 into the calculation in step 3.
If the actual flow rate in the fresh air duct cannot be directly measured, the following table may be used to 
estimate the Ventilate % setting required for adequate ventilation.  Note: using these values will not ensure 
ventilation meeting any particular code.

Summary of Contents for HHSC+

Page 1: ...ield Controls Healthy Home System Controller Plus HHSC is designed to work in conjunction with the forced air HVAC system to periodically introduce fresh air into the home by controlling an FAD Fresh...

Page 2: ...D damper for proper operation Remote Activation Terminals timer on off switch Carbon Monoxide CO detector with alarm contacts makeup air sensor multiples having dry contacts Auxiliary Output terminals...

Page 3: ...rbecue grills A minimum of 3 above ground is recommended to avoid ingress of leaf litter grass clippings etc Do not use a crawl space basement or attic as a source of intake air Always be sure to comp...

Page 4: ...ors if mounting on drywall 4 Secure mounting base to wall with 3 screws provided making sure all wires extend through hole in mounting base 5 Adjust length and routing of each wire to reach proper ter...

Page 5: ...page 5 TYPICAL WIRING DIAGRAMS Figure 1 Single Stage Heating Cooling Figure 2 Multi Stage Heating Cooling...

Page 6: ...page 6 TYPICAL WIRING DIAGRAMS con t WIRING TO OPTIONAL EXHAUST FAN AND OR OPTIONAL REMOTE OVERRIDE DEVICES Figure 3 Heat Pump Figure 4 Exhaust Fan Override Device Control...

Page 7: ...mes the exhaust fan may be locally controlled by a wall switch or timer wired in parallel with the relay These terminals may also be used as 24 VAC input to control a device having 24 VAC control term...

Page 8: ...tions are 1 year 2 years and None if no UVC lamp systems have been installed or if no reminder is desired The Filter change timer will cause the HHSC status LED to turn red and display a message remin...

Page 9: ...de the constant flow rate from the table by the actual fresh air flow rate measured and multiply by 100 Ventilation 50 140 x 100 36 rounding up For this example setting the Ventilation at 36 will ensu...

Page 10: ...ble Enable System Clock 12 34PM 03 10 13 Replace UV Lamp Interval 1YR 2YR NONE UV Lamp R Reset Timer Fan Cycle Period Cycle Period 30 45 60 MINUTES SET CYCLE PERIOD 30 45 60 MINUTES 10 34AM 03 10 13 S...

Page 11: ...O YES Replace Filter Months 3 6 12 NONE Filter Remaining Days Reset Timer NO YES 03 10 13 TES 10 45AM 04 10 13 SET MONTH 10 45AM 04 23 13 SET DAY 10 45AM 04 23 13 SET YEAR rt 10 35PM System Inhibit du...

Page 12: ...ire is not connected to the HHSC the HHSC will automatically disable the feature If this feature is to be enabled ensure that the FAD damper pigtail s yellow wire is connected to terminal VS IN and se...

Page 13: ...utomatically INHIBIT MODE This feature allows the occupants to set a daily period in which the HHSC will be prohibited from causing the HVAC system fan to run according to the programmed Ventilate Cir...

Page 14: ...mper malfunction if enabled Service is required to correct the malfunction the alert will automatically reset when the malfunction is corrected or the Damper Monitor feature is disabled The internal b...

Page 15: ...main idle for the remainder of the Fan Cycle Period when it will begin a new cycle or the system thermostat calls for new HVAC action ACTIVATION BY REMOTE OVERRIDE DEVICE S Remote device s having dry...

Page 16: ...en red and white close 4 Verify continuity in the wiring between the damper and the HHSC PROBLEM A C TURNS ON DURING FAN CYCLING CALLS SOLUTION CHECK 1 Verify wiring conforms to appropriate wiring dia...

Page 17: ...SPECIFICATIONS FRESH AIR DAMPER Electrical Minimum Wiring Requirements 18AWG 24 VAC Maximum Voltage 30 VAC Maximum Operating Current 0 1 Amps Power Draw Requirement 3W at 24VAC when opening or closin...

Page 18: ...page 18...

Page 19: ...page 19...

Page 20: ...52 522 3031 Fax 252 522 0214 www fieldcontrols com Field Controls LLC P N 46633800 Rev A 07 15 Warranty For warranty information about this or any Field Controls product visit www fieldcontrols com wa...

Reviews: