Field Controls HHSC+ User Manual Download Page 12

page 12

Circulate % may be set equal to or greater than the Ventilate %, to cause the HVAC fan to run longer per 
cycle, for extra circulation, filtration, and UVC treatment if desired, or if the HHSC is used for circulation 
only.  For instance, if Ventilate % is set to 33% and Circulate % is set to 50%, with the cycle period set to 30 
minutes, every thirty minutes the HHSC+ will activate the HVAC fan, open the FAD damper for 10 minutes, 
and continue to run the fan for another 5 minutes (.33 x 30 = 10, .50 x 30 = 15) if the thermostat does not 
cause the fan to run during the period. 

Circulate % may not be set less than Ventilate %, because the HVAC fan must operate when the FAD 
damper is commanded to be open by the HHSC+.  The Circulate % setting will automatically “follow” the 
Ventilate % setting if it is adjusted higher, but will not “follow” it lower. 

DAMPER MONITOR

The HHSC+ can continuously monitor the FAD fresh air damper for proper operation, if the feature is 
enabled and the yellow wire from the damper pigtail (included) is connected to terminal VS-IN on the 
HHSC+ (see Figures 1,2, 3).  If enabled and the HHSC+ repeatedly detects a malfunction of the damper, 
the status LED will turn to red, and the display will indicate that a damper malfunction has been detected.  
NOTE: this feature is optional and may be disabled if desired.  If the yellow pigtail wire is not connected to 
the HHSC+, the HHSC+ will automatically disable the feature.

If this feature is to be enabled, ensure that the FAD damper pigtail’s yellow wire is connected to terminal VS-
IN, and select “Automatic” in the Damper Monitor menu item window.  The HHSC+ will then automatically 
test the damper and its connection.  If the damper responds properly, the display will indicate that the 
damper is detected and the Damper Monitor feature will be enabled.  If the damper does not respond 
properly or the yellow wire is not connected, the HHSC+ will automatically disable the feature.  

This feature may also be disabled manually at any time by selecting the Damper Monitor menu item 
window and selecting “Disabled”, even if the yellow pigtail wire is connected.  If an outdoor thermostat or 
other device is used to prohibit fresh air ventilation when extreme outdoor conditions exist (wired in series 
between the FAD blue wire and terminal VO, see (Figure 6), the feature must be disabled to prohibit false 
malfunction detection.

Daylight Savings Time mode:  If this feature is enabled, the HHSC+ will automatically adjust its clock time 
by changing the time by one hour on the specified dates for transitioning to or from Daylight Savings time 
to Standard time, regardless of the time zone.  This feature is important for keeping the Inhibit Mode time 
schedule correct (see Inhibit Mode feature section), without any changes needed by the user.  This feature 
may be disabled for those areas that do not observe Daylight Savings Time changes. 

Summary of Contents for HHSC+

Page 1: ...ield Controls Healthy Home System Controller Plus HHSC is designed to work in conjunction with the forced air HVAC system to periodically introduce fresh air into the home by controlling an FAD Fresh...

Page 2: ...D damper for proper operation Remote Activation Terminals timer on off switch Carbon Monoxide CO detector with alarm contacts makeup air sensor multiples having dry contacts Auxiliary Output terminals...

Page 3: ...rbecue grills A minimum of 3 above ground is recommended to avoid ingress of leaf litter grass clippings etc Do not use a crawl space basement or attic as a source of intake air Always be sure to comp...

Page 4: ...ors if mounting on drywall 4 Secure mounting base to wall with 3 screws provided making sure all wires extend through hole in mounting base 5 Adjust length and routing of each wire to reach proper ter...

Page 5: ...page 5 TYPICAL WIRING DIAGRAMS Figure 1 Single Stage Heating Cooling Figure 2 Multi Stage Heating Cooling...

Page 6: ...page 6 TYPICAL WIRING DIAGRAMS con t WIRING TO OPTIONAL EXHAUST FAN AND OR OPTIONAL REMOTE OVERRIDE DEVICES Figure 3 Heat Pump Figure 4 Exhaust Fan Override Device Control...

Page 7: ...mes the exhaust fan may be locally controlled by a wall switch or timer wired in parallel with the relay These terminals may also be used as 24 VAC input to control a device having 24 VAC control term...

Page 8: ...tions are 1 year 2 years and None if no UVC lamp systems have been installed or if no reminder is desired The Filter change timer will cause the HHSC status LED to turn red and display a message remin...

Page 9: ...de the constant flow rate from the table by the actual fresh air flow rate measured and multiply by 100 Ventilation 50 140 x 100 36 rounding up For this example setting the Ventilation at 36 will ensu...

Page 10: ...ble Enable System Clock 12 34PM 03 10 13 Replace UV Lamp Interval 1YR 2YR NONE UV Lamp R Reset Timer Fan Cycle Period Cycle Period 30 45 60 MINUTES SET CYCLE PERIOD 30 45 60 MINUTES 10 34AM 03 10 13 S...

Page 11: ...O YES Replace Filter Months 3 6 12 NONE Filter Remaining Days Reset Timer NO YES 03 10 13 TES 10 45AM 04 10 13 SET MONTH 10 45AM 04 23 13 SET DAY 10 45AM 04 23 13 SET YEAR rt 10 35PM System Inhibit du...

Page 12: ...ire is not connected to the HHSC the HHSC will automatically disable the feature If this feature is to be enabled ensure that the FAD damper pigtail s yellow wire is connected to terminal VS IN and se...

Page 13: ...utomatically INHIBIT MODE This feature allows the occupants to set a daily period in which the HHSC will be prohibited from causing the HVAC system fan to run according to the programmed Ventilate Cir...

Page 14: ...mper malfunction if enabled Service is required to correct the malfunction the alert will automatically reset when the malfunction is corrected or the Damper Monitor feature is disabled The internal b...

Page 15: ...main idle for the remainder of the Fan Cycle Period when it will begin a new cycle or the system thermostat calls for new HVAC action ACTIVATION BY REMOTE OVERRIDE DEVICE S Remote device s having dry...

Page 16: ...en red and white close 4 Verify continuity in the wiring between the damper and the HHSC PROBLEM A C TURNS ON DURING FAN CYCLING CALLS SOLUTION CHECK 1 Verify wiring conforms to appropriate wiring dia...

Page 17: ...SPECIFICATIONS FRESH AIR DAMPER Electrical Minimum Wiring Requirements 18AWG 24 VAC Maximum Voltage 30 VAC Maximum Operating Current 0 1 Amps Power Draw Requirement 3W at 24VAC when opening or closin...

Page 18: ...page 18...

Page 19: ...page 19...

Page 20: ...52 522 3031 Fax 252 522 0214 www fieldcontrols com Field Controls LLC P N 46633800 Rev A 07 15 Warranty For warranty information about this or any Field Controls product visit www fieldcontrols com wa...

Reviews: