Field Controls HHSC+ User Manual Download Page 14

page 14

SAVING THE SETUP

While in the Menu = Continue/Select = Save & Exit window, press SELECT to save the setup settings, exit 
to the normal operation display window and begin normal operation, or MENU to continue with viewing the 
available menu items and settings.  

If no buttons are pushed for three minutes, any changes to settings will be automatically saved and the 
HHSC+ will return to normal operation with any changes to settings taking effect immediately.

NORMAL OPERATION DISPLAY AND LED STATUS

Under normal operation, the status LED will glow steady green and the HHSC+ display will show the current 
time and date on the upper display line. On the lower display line, “FAN ON” will be displayed if the HVAC 
fan is on (from either thermostat command or HHSC+ program), and “VENT ON” if the FAD vent damper 
is open.  
The status LED will glow steady red, and the display will show an alert message, if action is required for 
service or maintenance:

•  UV lamp replacement:  the selected period for replacing UVC germicidal lamp(s) has expired.  

Replace the lamp(s) and reset the timer by following the instruction on the display.

•  HVAC filter replacement:  the selected period for replacing the HVAC system filter(s) has expired.  

Replace the filter(s) and reset the timer by following the instruction on the display.

•  Damper Malfunction:  the HHSC+ has detected an FAD fresh air damper malfunction (if enabled).  

Service is required to correct the malfunction; the alert will automatically reset when the malfunction is 
corrected, or the Damper Monitor feature is disabled.

•  The internal backup battery has become weak and is in need of replacement.

OPERATION

INDEPENDENT OPERATION

The HHSC+ will command the HVAC fan to operate periodically for a specific length of time, as governed 
by the chosen Fan Cycle Period and Circulate % settings, for a length of time (in minutes) equal to 

Fan On time = Fan Cycle Period setting (minutes) X Circulate % ÷ 100

Also, the HHSC+ will command the FAD vent damper to open, and the Auxiliary Output terminals will be 
energized (24 VAC), at the beginning of each fan cycle, for a length of time (in minutes) equal to 

Vent On time = Fan Cycle Period setting (minutes) X Ventilate % ÷ 100

If the Damper Monitor feature is enabled, the Auxiliary Output terminals will not energize until the FAD 
damper opens fully and communicates back to the HHSC+ by energizing the VS-In terminal via the FAD 
pigtail’s yellow wire; otherwise, the Auxiliary Output will be energized immediately.  The FAD damper and 
Auxiliary Output will not be activated for a longer time than the HVAC fan will be commanded to run, but 
they may be activated for a shorter time.

At the expiration of the Fan On time, the HHSC+ will end the commands to the FAD damper, the HVAC 
fan, and the Auxiliary Output.  The HHSC+ will then remain idle for the remainder of the Fan Cycle Period, 
when it will begin a new cycle, or the system thermostat calls for action, as described below.

Summary of Contents for HHSC+

Page 1: ...ield Controls Healthy Home System Controller Plus HHSC is designed to work in conjunction with the forced air HVAC system to periodically introduce fresh air into the home by controlling an FAD Fresh...

Page 2: ...D damper for proper operation Remote Activation Terminals timer on off switch Carbon Monoxide CO detector with alarm contacts makeup air sensor multiples having dry contacts Auxiliary Output terminals...

Page 3: ...rbecue grills A minimum of 3 above ground is recommended to avoid ingress of leaf litter grass clippings etc Do not use a crawl space basement or attic as a source of intake air Always be sure to comp...

Page 4: ...ors if mounting on drywall 4 Secure mounting base to wall with 3 screws provided making sure all wires extend through hole in mounting base 5 Adjust length and routing of each wire to reach proper ter...

Page 5: ...page 5 TYPICAL WIRING DIAGRAMS Figure 1 Single Stage Heating Cooling Figure 2 Multi Stage Heating Cooling...

Page 6: ...page 6 TYPICAL WIRING DIAGRAMS con t WIRING TO OPTIONAL EXHAUST FAN AND OR OPTIONAL REMOTE OVERRIDE DEVICES Figure 3 Heat Pump Figure 4 Exhaust Fan Override Device Control...

Page 7: ...mes the exhaust fan may be locally controlled by a wall switch or timer wired in parallel with the relay These terminals may also be used as 24 VAC input to control a device having 24 VAC control term...

Page 8: ...tions are 1 year 2 years and None if no UVC lamp systems have been installed or if no reminder is desired The Filter change timer will cause the HHSC status LED to turn red and display a message remin...

Page 9: ...de the constant flow rate from the table by the actual fresh air flow rate measured and multiply by 100 Ventilation 50 140 x 100 36 rounding up For this example setting the Ventilation at 36 will ensu...

Page 10: ...ble Enable System Clock 12 34PM 03 10 13 Replace UV Lamp Interval 1YR 2YR NONE UV Lamp R Reset Timer Fan Cycle Period Cycle Period 30 45 60 MINUTES SET CYCLE PERIOD 30 45 60 MINUTES 10 34AM 03 10 13 S...

Page 11: ...O YES Replace Filter Months 3 6 12 NONE Filter Remaining Days Reset Timer NO YES 03 10 13 TES 10 45AM 04 10 13 SET MONTH 10 45AM 04 23 13 SET DAY 10 45AM 04 23 13 SET YEAR rt 10 35PM System Inhibit du...

Page 12: ...ire is not connected to the HHSC the HHSC will automatically disable the feature If this feature is to be enabled ensure that the FAD damper pigtail s yellow wire is connected to terminal VS IN and se...

Page 13: ...utomatically INHIBIT MODE This feature allows the occupants to set a daily period in which the HHSC will be prohibited from causing the HVAC system fan to run according to the programmed Ventilate Cir...

Page 14: ...mper malfunction if enabled Service is required to correct the malfunction the alert will automatically reset when the malfunction is corrected or the Damper Monitor feature is disabled The internal b...

Page 15: ...main idle for the remainder of the Fan Cycle Period when it will begin a new cycle or the system thermostat calls for new HVAC action ACTIVATION BY REMOTE OVERRIDE DEVICE S Remote device s having dry...

Page 16: ...en red and white close 4 Verify continuity in the wiring between the damper and the HHSC PROBLEM A C TURNS ON DURING FAN CYCLING CALLS SOLUTION CHECK 1 Verify wiring conforms to appropriate wiring dia...

Page 17: ...SPECIFICATIONS FRESH AIR DAMPER Electrical Minimum Wiring Requirements 18AWG 24 VAC Maximum Voltage 30 VAC Maximum Operating Current 0 1 Amps Power Draw Requirement 3W at 24VAC when opening or closin...

Page 18: ...page 18...

Page 19: ...page 19...

Page 20: ...52 522 3031 Fax 252 522 0214 www fieldcontrols com Field Controls LLC P N 46633800 Rev A 07 15 Warranty For warranty information about this or any Field Controls product visit www fieldcontrols com wa...

Reviews: