Field Controls HHSC+ User Manual Download Page 15

page 15

ACTIVATION BY THERMOSTAT

The HHSC+ monitors the activity of the thermostat and performs operations as described here.  If the 
thermostat issues a demand for heating or cooling, or the HVAC fan is manually switched on, before an 
HHSC Fan On or Fan Cycle Period time expires (see Independent Operation above), the HHSC+ will 
immediately begin a new Fan Cycle period.  The HHSC+ will then command the FAD vent damper to open, 
and the Auxiliary Output terminals will be appropriately energized, for the Fan On and Vent On times as 
stated above.  The HVAC fan will also be commanded to run by the HHSC+ if either a cooling demand 
occurs, or if the fan is manually switched on at the thermostat.

NOTE:  The HHSC+ will not give a command to run the HVAC fan if a demand for heating only occurs.  
The HVAC system will operate the fan independently when this occurs.  This is also true when there is 
a demand for cooling, but the HHSC+ merely transmits the fan on command which is issued by the 
thermostat.

If the thermostat becomes satisfied and terminates the command for heating or cooling, or the fan is 
manually switched to Off or Auto while there is no current demand for heating or cooling, the HHSC Fan 
ON and Vent On times will be cut off, and the HHSC+ will terminate the commands to the FAD damper, 
the HVAC fan, and the Auxiliary Output.  The HHSC+ will then remain idle for the remainder of the Fan 
Cycle Period, when it will begin a new cycle, or the system thermostat calls for new HVAC action.

ACTIVATION BY REMOTE (OVERRIDE) DEVICE(S)

Remote device(s) having dry contacts, such as simple wall switches, timers, CO alarm contacts, pressure 
switches etc. may be used for remote activation of the HHSC+ ventilation system. Multiple such devices 
may be connected to the AUX-IN and R terminals in parallel (see Fig. 4); if any of these devices complete 
an electrical connection between R and AUX-IN, the HHSC+ will activate the HVAC fan, open the FAD 
damper, and activate the Auxiliary Out terminals, for as long as any of the remote devices are closed.

NOTE:  Do not directly connect any devices having solely electronic means of switching electrical current 
(transistor or triac switching), such as many current sensing relays; electrical leakage through such devices 
may cause improper operation of the system and may damage the HHSC+ and/or other remote devices.  If 
such a device is to be used, install an isolation relay between the HHSC+ and the device.

POWER OUTAGE

If a power outage occurs, the HHSC+ will resume normal operation after about 15 seconds after power is 
restored, with all settings as they were prior to the outage, and will display the correct time and date.  The 
display and LED will not show or be illuminated, but the internal backup battery will continue to maintain the 
time, date, and filter and UV lamp replacement timers; no corrections are required.  Battery life is in excess 
of one year under such conditions.

Summary of Contents for HHSC+

Page 1: ...ield Controls Healthy Home System Controller Plus HHSC is designed to work in conjunction with the forced air HVAC system to periodically introduce fresh air into the home by controlling an FAD Fresh...

Page 2: ...D damper for proper operation Remote Activation Terminals timer on off switch Carbon Monoxide CO detector with alarm contacts makeup air sensor multiples having dry contacts Auxiliary Output terminals...

Page 3: ...rbecue grills A minimum of 3 above ground is recommended to avoid ingress of leaf litter grass clippings etc Do not use a crawl space basement or attic as a source of intake air Always be sure to comp...

Page 4: ...ors if mounting on drywall 4 Secure mounting base to wall with 3 screws provided making sure all wires extend through hole in mounting base 5 Adjust length and routing of each wire to reach proper ter...

Page 5: ...page 5 TYPICAL WIRING DIAGRAMS Figure 1 Single Stage Heating Cooling Figure 2 Multi Stage Heating Cooling...

Page 6: ...page 6 TYPICAL WIRING DIAGRAMS con t WIRING TO OPTIONAL EXHAUST FAN AND OR OPTIONAL REMOTE OVERRIDE DEVICES Figure 3 Heat Pump Figure 4 Exhaust Fan Override Device Control...

Page 7: ...mes the exhaust fan may be locally controlled by a wall switch or timer wired in parallel with the relay These terminals may also be used as 24 VAC input to control a device having 24 VAC control term...

Page 8: ...tions are 1 year 2 years and None if no UVC lamp systems have been installed or if no reminder is desired The Filter change timer will cause the HHSC status LED to turn red and display a message remin...

Page 9: ...de the constant flow rate from the table by the actual fresh air flow rate measured and multiply by 100 Ventilation 50 140 x 100 36 rounding up For this example setting the Ventilation at 36 will ensu...

Page 10: ...ble Enable System Clock 12 34PM 03 10 13 Replace UV Lamp Interval 1YR 2YR NONE UV Lamp R Reset Timer Fan Cycle Period Cycle Period 30 45 60 MINUTES SET CYCLE PERIOD 30 45 60 MINUTES 10 34AM 03 10 13 S...

Page 11: ...O YES Replace Filter Months 3 6 12 NONE Filter Remaining Days Reset Timer NO YES 03 10 13 TES 10 45AM 04 10 13 SET MONTH 10 45AM 04 23 13 SET DAY 10 45AM 04 23 13 SET YEAR rt 10 35PM System Inhibit du...

Page 12: ...ire is not connected to the HHSC the HHSC will automatically disable the feature If this feature is to be enabled ensure that the FAD damper pigtail s yellow wire is connected to terminal VS IN and se...

Page 13: ...utomatically INHIBIT MODE This feature allows the occupants to set a daily period in which the HHSC will be prohibited from causing the HVAC system fan to run according to the programmed Ventilate Cir...

Page 14: ...mper malfunction if enabled Service is required to correct the malfunction the alert will automatically reset when the malfunction is corrected or the Damper Monitor feature is disabled The internal b...

Page 15: ...main idle for the remainder of the Fan Cycle Period when it will begin a new cycle or the system thermostat calls for new HVAC action ACTIVATION BY REMOTE OVERRIDE DEVICE S Remote device s having dry...

Page 16: ...en red and white close 4 Verify continuity in the wiring between the damper and the HHSC PROBLEM A C TURNS ON DURING FAN CYCLING CALLS SOLUTION CHECK 1 Verify wiring conforms to appropriate wiring dia...

Page 17: ...SPECIFICATIONS FRESH AIR DAMPER Electrical Minimum Wiring Requirements 18AWG 24 VAC Maximum Voltage 30 VAC Maximum Operating Current 0 1 Amps Power Draw Requirement 3W at 24VAC when opening or closin...

Page 18: ...page 18...

Page 19: ...page 19...

Page 20: ...52 522 3031 Fax 252 522 0214 www fieldcontrols com Field Controls LLC P N 46633800 Rev A 07 15 Warranty For warranty information about this or any Field Controls product visit www fieldcontrols com wa...

Reviews: