T

ESTING

 

1. 

With the unit plugged in and the discharge line in place, pour water into the pump reservoir until the unit activates to 
verify the unit works. 

2. 

To test the overflow safety circuit (Models 20+ULS and 20+ULST only): 
a. 

Energize the appliance so it runs. 

b. 

Kink the tube coming from the pump discharge, or unplug the power cord, so it cannot pump out. 

c. 

Pour water into the pump reservoir, filling it completely. 

d. 

As the water level nears the top of the unit the overflow safety switch should activate, breaking the thermostat 
circuit to the appliance (or triggering an alarm circuit, if used.) 

e. 

Un-kink the tube, or plug the cord back in, and allow the pump to empty the tank.  As the water level goes down 
the overflow safety switch will deactivate and the appliance will energize again (or the alarm will reset.) 

MAINTENANCE 

WARNING:

 

Before attempting any maintenance on the unit, disconnect the power cord from the power supply to 

reduce the risk of electric shock.  Also, take whatever precautions are necessary if the safety overflow switch is 
wired to a thermostat or alarm circuit.

 

S

ERVICING OF A DOUBLE

-

INSULATED APPLIANCE

 

In a double-insulated product, two systems of insulation are provided instead of grounding.  No grounding means is 
provided on a double-insulated product, nor should a means for grounding be added to the product.  Servicing a double-
insulated product requires extreme care and knowledge of the system, and should be done only by qualified service 
personnel.  Replacement parts for a double-insulated product must be identical to the parts they replace.  A double-
insulated product is marked with the words “DOUBLE INSULATION” OR “DOUBLE INSULATED” 

If the unit does not perform as stated in the above tests, remove the two screws holding the cover from the deck, and 
remove the cover.  Verify that the float mechanism moves up and down freely.  If the float binds, it may be dirty or 
damaged.  Since the motor is totally enclosed, no maintenance is required on the motor.  However, the tank and float may 
need to be cleaned periodically.  Simply remove the four screws at the corners of the pump deck and lower the tank.  The 
tank can now be cleaned with a mild detergent.  Use a damp cloth to wipe off the float if necessary.  The impeller may 
need to be cleaned as well. 

R

EFER TO THE FOLLOWING IN ORDER TO CLEAN THE IMPELLER

 

1. 

Remove the entire pump from the mounting wall. 

2. 

Disassemble the tank from the deck by removing the four screws in the corners of the deck. 

3. 

Turn the unit upside down and remove the impeller cover by loosening the five screws on the underside of the motor. 

4. 

The impeller and shaft assembly may then be removed and cleaned.  The impeller chamber should be cleaned at 
this time as well. 

5. 

Wipe off the gasket between the impeller cover and the motor housing with a damp cloth before reassembling the 
impeller to the motor. 

6. 

Reassemble the tank to the deck and reinstall the pump. 

R

EFER TO THE FOLLOWING TO CLEAN THE CHECK VALVE AND VERIFY ITS OPERATION

 

1. 

Remove the discharge line from the check valve. 

2. 

Use a 9/16" wrench to remove the check valve from the deck of the pump. 

3. 

Visually check the valve for obstructions.  If damaged, replace. 

4. 

To re-install the check valve, hand tighten it into the deck.  Then, tighten 1/2 turn further with a wrench.  Be careful 
not to over-tighten as this may distort the O-ring seal under the check valve. 

Summary of Contents for 20+

Page 1: ...RT NUMBER DESCRIPTION 20 UL 115VAC 60Hz 1 45 Amps 46296901 Base Model 20 ULS 115VAC 60Hz 1 45 Amps 46296902 Base Model with Overflow Safety Switch 20 ULT 115VAC 60Hz 1 45 Amps 46296903 Base Model with...

Page 2: ...ible tubing or rigid pipe but must be no larger than 3 8 I D Extend the discharge line straight up from the pump to the highest point possible without exceeding the head GPH capacity of the pump befor...

Page 3: ...ble insulated product is marked with the words DOUBLE INSULATION OR DOUBLE INSULATED If the unit does not perform as stated in the above tests remove the two screws holding the cover from the deck and...

Page 4: ...en running a Check the tank for debris and clean if necessary The impeller may also be cleaned if needed Refer to the maintenance section above for cleaning instructions 3 Unit runs but does not pump...

Page 5: ...iliser un raccord en T pour joindre le tuyau de trop plein et le tuyau d vacuation principal avant qu ils p n trent dans la pompe Voir Le Sch ma 1 2 Brancher une ligne de d charge au clapet de retenue...

Page 6: ...arme ENTRETIEN D UN APPAREIL DOUBLE ISOLATION Pour un produit double isolation deux syst mes d isolation sont fournis au lieu d une mise la terre Aucun dispositif de mise la terre n est fourni avec un...

Page 7: ...ac e e V rifier s il y a obstruction de la des ligne s d vacuation dans la pompe Nota en cas d obstruction persistante il se peut que l appareil soit endommag 2 La pompe fait beaucoup de bruit lorsqu...

Page 8: ...aporador o desde el generador es posible que sea necesario derivar el rebose y el desag e principal juntos antes de que entren en la bomba Ver Figura 1 2 Conecte una l nea de descarga a la v lvula de...

Page 9: ...circuito de alarma SERVICIO A UN APARATO DE AISLAMIENTO DOBLE En un producto de aislamiento doble se suministran dos sistema de aislamiento en lugar de una puesta a tierra En un producto de aislamient...

Page 10: ...r reemplazada e Verifique que no hayan obstrucciones en la s l nea s de desag e hacia la bomba Nota Si estas l neas est n tapadas y permanecen tapadas el aparato se perjudicar 2 La bomba hace mucho ru...

Page 11: ...E LIMITE LA R PARATION OU AU REMPLACEMENT D UN PRODUIT D FECTUEUX SAUF SI LES DOMMAGES D COULENT DU FAIT QUE FIELD NE RESPECTE PAS LES LOIS F D RALES OU PROVINCIALES SUR LES GARANTIES FIELD N EST RESP...

Page 12: ...Page 12 PN CONPUMP Rev C 08 00...

Reviews: