Parameter 172: ON/OFF mode
This mode is necessary while connecting non-dimmable light sources. Setting this parameter to 1 automatically ignores brightening/dimming time settings. Forced
auto-calibration will set this parameters value to 2.
Size: 1 Byte, Default Value: 2
Setting
Description
0
ON/OFF mode disabled (dimming is possible)
1
ON/OFF mode enabled (dimming is not possible)
2
mode selected automatically
Parameter 173: Dimmability of the load (read only)
This parameter allows to read if the load detected during calibration procedure is dimmable.
Size: 1 Byte, Default Value: 0
Setting
Description
0
load recognized as dimmable
1
load recognized as non-dimmable
Parameter 174: Soft-start functionality
This parameter allows to set time required to warm up the filament of halogen bulb.
Size: 1 Byte, Default Value: 1
Setting
Description
0
no soft-start
1
short soft-start (0.1s)
2
long soft-start (0.5s)
Parameter 175: Auto-calibration after power on
This parameter determines the trigger of auto-calibration procedure, e.g. power on, loaderror, etc.
Size: 1 Byte, Default Value: 1
Setting
Description
0
no auto-calibration after power on
2
Auto-calibration after each power on
3
Auto-calibration after each LOAD ERROR (no load, load failure, burnt out bulb), if parameter 176 is set to 1 also
after SURGE (output overvoltage) and OVERCURRENT (output overcurrent)
4
Auto-calibration after each power on or after each LOAD ERROR (no load, load failure, burnt out bulb), if
parameter 176 is set to 1 also after SURGE (output overvoltage) and OVERCURRENT (output overcurrent)
Parameter 176: Behaviour after OVERCURRENT or SURGE
Error occurrences related to surge or overcurrent results in turning off the output to prevent possible malfunction. By default the device performs three attempts to
turn on the load (useful in case of temporary, short failures of the power supply).
Size: 1 Byte, Default Value: 1
Setting
Description
0
device permanently disabled until re-enabling by command or external switch
1
three attempts to turn on the load
Parameter 177: Brightness level correction for flickering loads
Correction reduces spontaneous flickering of some capacitive loads (e.g. dimmable LEDs) at certain brightness levels in 2-wire installation.In countries using
ripple-control, correction may cause changes in brightness. In this case it is necessary to disable correction or adjust the time of correction for flickering loads.
Size: 2 Byte, Default Value: 255
Setting
Description
0
automatic correction disabled
1 - 254
(1-254s, 1s step)duration of correction
255
automatic correction always enabled
Parameter 178: Method of calculating the active power
This parameter defines how to calculate active power. It is useful in a case of 2-wire connection with light sources other than resistive.
Size: 1 Byte, Default Value: 0