FlameSpec
IR3-H2-HD
User Manual
F140V0020.03
For more information & Technical support: (+1) 714-671-8500 · [email protected]
5
2.2
Preparations for Installation
The installation must comply with local regulations and standards applicable to flame detectors (e.g.,
NFPA 72) and all local and common engineering practices. It is recommended to consult with a safety
engineer.
The detectors can be installed with the use of general-purpose common tools and equipment.
Prior to installation:
•
Verify the appropriate purchase order.
•
Record the part and serial numbers of the detectors and the installation date and log.
•
Visually inspect the detector prior to installation to make sure it is intact.
•
Make sure that you have all the components and tools required to complete the
detector installation readily available before beginning installation. In cases where you
cannot complete the installation in a single session, secure and seal the detectors and
conduits before leaving the site.
•
Use color-coded conductors or suitable wire markings or labels for the wiring. You may
use 12 to 20 AWG (2.5
𝑚𝑚
2
to 0.35
𝑚𝑚
2
) wires for the site wiring. The selection of
wire gauge should be based on the number of detectors used on the same line and the
distance from the control unit, in compliance with specifications.
•
Use wire rated for a temperature of at least 111°C, which is 5°C above the rated service
temperature.
2.3
Required Tools
The detector can be installed using general purpose common tools as defined in the following table:
Tool
Function
Hex. KEY 6 mm
Vertical alignment
Hex. KEY 10 mm
Horizontal alignment
Wrench 13 mm
Mounting the detector
Flat Screwdriver 6 mm
Ground screw connection
Flat screwdriver 3.5mm
Terminal connection
2.4
Certification Instructions
Warning
: Do not open the detector, even when isolated, when flammable atmosphere present.
•
The equipment may be used in hazardous areas with flammable gasses and vapors with
apparatus groups IIC, IIB and IIA and with temperature classes T1, T2, T3, T4 and T5. See
details of the explosion proof approvals in section 6.7.
•
The equipment is certified for use in ambient temperatures in the range of -67°F to
+167°F (-55°C to +75°C) or -67°F to +185°F (-55°C to +85°C) and should not be used in
temperatures outside this range.