DCP-10
Page 22/27
5
LOP switch
low level is active
6
HET switch
low level is active
7
Emergency stop
low level is active
8
Remote start signal
low level is active
9
Reserved
low level is active
10
Gen Aux. Switch closed
low level is active
11
Low fuel level
low level is active
12
Lamp test
low level is active
8.8 The optional items for configurable output:
Code
Failure Type Define
Code
Failure Type Define
0
Not used
1
Over current tripping
2
Alarm
3
Pre-alarm
4
Idle 0 (N.C.)
5
Preheat
6
Speed up
7
Reserved
8
Fuel pump control
9
Running
10
System in AUTO mode
11
Reserved
12
System in MAN mode
13
Reserved
14
Idle 1 (N.O.)
15
Reserved
16
GCB failure (within 5s)
17
Fail to start
NOTE:
If define one configurable relay as Speed up, the relay will close after the
engine has successfully started. If there is idle function, the relay will
close after idle timer times out.