8.5 Calibration Menu:
NO.
Items
Preset
Value Range
5.1
GEN. V1 offset
±
10.0%
5.2
GEN. V2 offset
±
10.0%
5.3
GEN. V3 offset
±
10.0%
5.4
Current I1 offset
±
10.0%
5.5
Current I2 offset
±
10.0%
5.6
Current I3 offset
±
10.0%
5.7
Pressure offset
±
10.0%
5.8
Temperature offset
±
10.0%
5.9
Batt. V offset
±
10.0%
8.6 The optional items for P/T-sensor:
Code
The brand model of LOP sensor
The brand model of HET sensor
0
not used
not used
1
close for low oil pressure
close for high temperature
2
open for low oil pressure
open for high temperature
3
VDO 5 bar
VDO 120
℃
4
VDO 10 bar
VDO 150
℃
5
Datcon 7 bar
Datcon
6
Murphy 7 bar
Murphy
7
Pre-set 1
PT100
8
Pre-set 2
Pre-set 1
9
Pre-set 3
Pre-set 2
10
Pre-set 4
Pre-set 3
11
configured by user
Pre-set 4
12
configured by user
NOTE:
When the controller leaves factory, the optional types and functions of
LOP sensor and HET sensor have been preset as the above table. If the
using sensor is not listed in this table, the user can select “configurable”,
and write sensor parameters to controller via software.
LOP sensor parameter addendum
:
VDO 5 bar:
VDO 10 bar:
P
(Bar)
0.0 0.5 1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5
P
(PSI)
0
7.3
14.5
21.8
29.0
36.3
43.5
50.8
58.0
65.3
72.5
R
(Ω)
11
29
47
65
82
100
117
134
151
167
184
P
(Bar)
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0 10.0
P
(PSI)
0
14.5
29.0
43.5
58.0
72.5
87.0 101.5 116.0 130.5 145.0
R
(Ω)
10
31
52
71
90
106
124
140
155
170
184