8.3 Engine Parameters:
NO.
Items
Preset
Value Range
3.1
Pair of poles
2
1-4
3.2
Fuel mode
0
0-1 / 0(NC) / 1 (NO)
3.3
T-sensor type
12
0-15 / 0 (not used)
3.4
P-sensor type
11
0-15 / 0 (not used)
3.5
Start delay
10S
0-300 S
3.6
Crank attempt
3 times
1-10 times
3.7
Crank time
5S
0-30 S
3.8
Crank rest
10S
0-300 S
3.9
Crank cutout RPM
300RPM
1-9999 RPM
3.10
Crank cutout Oil-P
1.0BAR
0.1-150.0BAR/999.9(
not set
)
3.11
cutout P-delay
0
1-60 S / 0(not set)
3.12
Idle delay
0
0-9999 S
3.13
Preheat delay
3S
0-300 S
3.14
Preheat mode
1
1-3
3.15
Safety-on delay
10S
0-600 S
3.16
Cool down delay
300S
0-600 S
3.17
Stop delay
20S
0-60 S
3.18
Under SP Alarm
0RPM
0-9999 RPM / 0 (not set)
3.19
Under SP preALM
1440RPM
0-9999 RPM / 0 (not set)
3.20
Over SP preALM
1600RPM
1-9999 RPM / 9999 (not set)
3.21
Over SP Alarm
1710RPM
1-9999 RPM / 9999 (not set)
3.22
Oil-P low Alarm
1.1BAR
0-45.0 BAR
3.23
Oil-P low preALM
1.4BAR
0-45.0 BAR
3.24
Coolant preALM
92
℃
70-320
℃
/ 9999 (not set)
3.25
Coolant Alarm
100
℃
70-320
℃
/ 9999 (not set)
3.26
Batt. Undervolt.
8.0V
1.0-25.0V / 0 (not set)
3.27
Batt. overvolt.
28.0V
1.0-35.0V / 99.9 (not set)
3.28
charge V Pre-alarm
8.0V
1.0-25.0V / 0 (not set)
8.4 Configurable Inputs and Outputs:
NO.
Items
Preset
Value Range
4.1
Configurable input 1
8
0-12 (define code as 8.7)
4.2
Configurable input 2
7
0-12 (define code as 8.7)
4.3
Configurable input 3
12
0-12 (define code as 8.7)
4.4
Input 1 delay
2S
0-60 S
4.5
Input 2 delay
2S
0-60 S
4.6
Input 3 delay
2S
0-60 S
4.7
Configurable relay 1
2
0-80 (define code as 8.8)
4.8
Configurable relay 2
3
0-80 (define code as 8.8)
4.9
Configurable relay 3
5
0-80 (define code as 8.8)
NOTE: D-Input Delay is only for 1 to 4 codes in 8.7.