Talentum UV/IR Test Unit Procedure 

 

 

 

0044-112-01 

 
How to test a Detector using the Test Unit 

To power up the unit, remove the Clip-on the base of the Test Unit, 

operate the power switch to ‘ON’

 

and t

he supply LED will illuminate ‘

g

reen’ if the battery has sufficient charge 

or flash if the battery is low. 

Care should be taken to ensure that the Test Unit is sufficiently charged when performing the test and 
that its bulb is working correctly. If the Test Unit is insufficiently charged or the bulb has failed, it is likely 
to result in test failure (no response from the detector). If testing a UV version of Talentum, turn on the 
UV lamp, using the switch at the back of the UV lamp unit. A green LED will indicate that the UV lamp 
unit is on. 

 

 

 

 

 

 

 

Hold  the  Test  Unit  as  still  as  possible  at  a  distance  of  approximately  50-70cm  (c.1-2¼  ft)  from  the 

detector, close to the centre of the detector’s line of sight, taking care to point the 

Test Unit emitter 

towards the detector’s sensors.

 

 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for Talentum UV/IR Test Unit

Page 1: ...t so that it is optimised for testing UV IR flame detectors Modifying the Test Unit with the adapter changes the output IR and UV spectrum so it closely matches a yellow flame This subjects the Talentum detector to a test more suited to identifying a performance issue The output of the torch without this modification matches a blue flame Health and Safety In accordance with the Talentum User Guide...

Page 2: ...he front of the torch including the four screws and washers and put them aside 3 Fit the modification assembly so that the seven optical filters are positioned over the test torch bulb and the UV source sits above the test torch on the keypad side as shown below 4 Take the new filter arrangement and without removing any parts use the four new screws to locate it on the front of the Test Unit Gentl...

Page 3: ...orming the test and that its bulb is working correctly If the Test Unit is insufficiently charged or the bulb has failed it is likely to result in test failure no response from the detector If testing a UV version of Talentum turn on the UV lamp using the switch at the back of the UV lamp unit A green LED will indicate that the UV lamp unit is on Hold the Test Unit as still as possible at a distan...

Page 4: ...nager for support Summary Test description Flame dimensions Distance to detector Test Unit with UV IR Adapter N A 50 70cm 1 2 ft Warranty Warranty is not affected by using these components with the test unit provided that no other modifications are implemented The test unit should still be serviced and maintained in accordance with the instructions The new free issue components carry a limited 1 y...

Reviews: