Talentum UV/IR Test Unit Procedure
0044-112-01
How to test a Detector using the Test Unit
To power up the unit, remove the Clip-on the base of the Test Unit,
operate the power switch to ‘ON’
and t
he supply LED will illuminate ‘
g
reen’ if the battery has sufficient charge
or flash if the battery is low.
Care should be taken to ensure that the Test Unit is sufficiently charged when performing the test and
that its bulb is working correctly. If the Test Unit is insufficiently charged or the bulb has failed, it is likely
to result in test failure (no response from the detector). If testing a UV version of Talentum, turn on the
UV lamp, using the switch at the back of the UV lamp unit. A green LED will indicate that the UV lamp
unit is on.
Hold the Test Unit as still as possible at a distance of approximately 50-70cm (c.1-2¼ ft) from the
detector, close to the centre of the detector’s line of sight, taking care to point the
Test Unit emitter
towards the detector’s sensors.