background image

Talentum UV/IR Test Unit Procedure 

 

 

 

0044-112-01 

How to modify the Test Unit 

1)

 

Remove the four screws that hold on the plate and filter that cover the bulb of the Test Unit 
using a 2.5mm allen/hex key;  
 

 
 
 
 
 
 
 
 
 
 

2)

 

Remove the black cover and the blue filter behind it from the front of the torch including the 
four screws and washers and put them aside. 

 

 

 

 

 

 

 

3)

 

Fit the modification assembly so that the seven optical filters are positioned over the test 
torch bulb and the UV source sits above the test torch on the keypad side as shown below 
 
 
 

 

 

 

 

 

4)  Take the new filter arrangement and, without removing any parts, use the four new screws to 
locate it on the front of the Test Unit.  Gently tighten the four screws so that the filter is held 
securely. 

 

Summary of Contents for Talentum UV/IR Test Unit

Page 1: ...t so that it is optimised for testing UV IR flame detectors Modifying the Test Unit with the adapter changes the output IR and UV spectrum so it closely matches a yellow flame This subjects the Talentum detector to a test more suited to identifying a performance issue The output of the torch without this modification matches a blue flame Health and Safety In accordance with the Talentum User Guide...

Page 2: ...he front of the torch including the four screws and washers and put them aside 3 Fit the modification assembly so that the seven optical filters are positioned over the test torch bulb and the UV source sits above the test torch on the keypad side as shown below 4 Take the new filter arrangement and without removing any parts use the four new screws to locate it on the front of the Test Unit Gentl...

Page 3: ...orming the test and that its bulb is working correctly If the Test Unit is insufficiently charged or the bulb has failed it is likely to result in test failure no response from the detector If testing a UV version of Talentum turn on the UV lamp using the switch at the back of the UV lamp unit A green LED will indicate that the UV lamp unit is on Hold the Test Unit as still as possible at a distan...

Page 4: ...nager for support Summary Test description Flame dimensions Distance to detector Test Unit with UV IR Adapter N A 50 70cm 1 2 ft Warranty Warranty is not affected by using these components with the test unit provided that no other modifications are implemented The test unit should still be serviced and maintained in accordance with the instructions The new free issue components carry a limited 1 y...