Talentum UV/IR Test Unit Procedure
0044-112-01
To activate the main output source, press and hold down the * button on the Test Unit. It does not need
to be waved back and forth as it already mimics the characteristic flicker of a real flame. The flame
detector is expected to alarm within 30 seconds.
If a device is found to be insensitive to this flame sensor test, please contact your FFE account manager
for support.
Summary
Test description
Flame dimensions
Distance to detector
Test Unit with UV/IR Adapter
(N/A)
50-70cm (1-2¼ ft)
Warranty
Warranty is not affected by using these components with the test unit, provided that no other
modifications are implemented. The test unit should still be serviced and maintained in accordance with
the instructions.
The new free-issue components carry a limited 1-year warranty against defects in manufacture, in
isolation from the rest of the Test Unit. Any damage resulting from wear and tear or improper use is
not covered by this warranty.
Part number: 1800-009