Festo Span Series Operating Instructions Manual Download Page 5

5.9 Menu structure

Measured  value indicator (RUN mode)

2)

OutA

Edit

bin

OutB

Edit

bin

InA

Edit

ANLG

Spec

Edit

MENU

_|¯

Fctn

_|¯|_

Fctn

d_|¯|_

Fctn

Out

0…10 V

1…5 V
4…20 mA

Filt

OFF, 

2, 

4, 8, ... 1024 ms

SP

SP.Lo

SP.Lo

0…

60

…100 % FS

1)

In.Hi

10…

100 

% FS

Unit

bar

, kPa, MPa, PSI, MMHG, inHG, iH20, kGF

SP.Hi

SP.Hi

0…

70

…100 % FS

1)

In.Lo

0

…90 

% FS

Z.AdJ

OFF

, ON

3)

HY

HY

0…

0.5

…90 % FS

1)

Sub.d

Unit

, SP, SP.Lo, SP.Hi, d.SP, || || || ||

t.obS

5…

200

…9999 ms

Eco

di.ON, 

5, 10, 20, 40, 80, 160, 320, 640 s

d.SP

0.5…

…50 % FS

1)

Out

bin

PNP

, NPN

LOGC

NO

, NC

Out

Pin3

bin, 

ANLG

2)

COLR

bLUE

, R.OFF, R.ON

Lock  Code

OFF

, 1…9999

MASt

OFF

, ON

Measured value indicator (RUN mode)

= Edit button

= A- or B-key

1)

The values refer to the respective measuring range. The display takes place in the selected unit.

2)

Not applicable with PN-PN variant

3)

Not valid with -B2 and -B11 variant (factory setting ON)

bold

= factory setting

Fig. 20

5.10 Zero point synchronisation (zero adjust)

Requirement:
– The sensor is ready for operation (RUN mode).
– [Z.AdJ] [ON] is set (

è

 Chap. 5.6).

– The measured value lies in the range 0 bar ± 3 % FS.

 Press the A- and B-key and Edit button simultaneously.

è

 [OK] appears. The zero point synchronisation was successful.

è

 [FAIL] appears. The zero point synchronisation was not successful. Check

requirements.

Note

If [Z.AdJ] [OFF] is set for a later time, the device takes over the factory setting
calibration values.

5.11 Teach switching points (TEACH mode)

Note

The process for teaching the switching outputs for OutA (A-key) and OutB (B-key) is
the same. In the following, the process is described using the switching output OutA.

Note

There is no Timeout in the TEACH mode. The sensor changes to the RUN mode
only after the entire teach process is ended.

Requirement: The sensor is ready for operation (RUN mode).
If the security code is activated, the parameter entry option is blocked: [Lock]
flashes.
 Enter the security code (

è

 Chap. 5.4).

1. Establish switching function in the EDIT mode (

è

 Chap. 5.5).

2. Create pressure value 1.
3. Press the A-key and Edit button.

è

 The current pressure value will then be adopted as the first teach point (TP1).

è

 [t-IN] flashes.

4. Create pressure value 2.
5. Press the A-key and Edit button.

è

 The current pressure value is adopted as the second teach point (TP2).

è

 Switch to the RUN mode.

6

Operation

Caution

Property damage due to high temperatures.
Extreme pneumatic conditions (high cycle rate with large pressure amplitude)
can heat the product above 80° C.
 Select the operating conditions (in particular the ambient temperature, pres­

sure amplitude, cycle rate, current consumption) such that the product does
not heat up above the maximum permitted operating temperature.

Restoring factory settings (restore)

Note

By resetting to factory settings, the current settings are lost.

1. Switch off the operating voltage.
2. Keep the A- and B-keys pressed down simultaneously.
3. Switch on the operating voltage.
4. Additionally press the Edit button.

è

 [Rsto] [PARM] appears. All parameters are reset to the factory settings

(

è

 Fig. 20).

7

Maintenance and care

1. Switch off the energy sources (operating voltage, compressed air).
2. Clean sensor with non-abrasive cleaning agents.

8

Disassembly

1. Switch off the energy sources (operating voltage, compressed air).
2. Separate connections from the sensor.
3. Loosen the mountings.

Reviews: