SFE1−LF−...
Festo SFE1−LF−... 0503NH English
33
Fe
a
t
u
re
T
ype
d
e
s
i
g
n
a
tion
Thermic mass flow sensor
SFE1−...
Design
−LF−... (Low Flow)
Flow range
−F10−...
(0.5...10 l/min)
−F200−...
(10...200 l/min)
Mechanical connection
−H...−... (hat rail) / −W...−... (wall)
Pneumatic connection
−...Q6−...: Quickstar QS6 / −...Q8−...: Quickstar QS8
Electric outputs
−P2..(2 PNP) / −N2.. (2 NPN)
..I−... : Analogue output 4...20 mA
..U−...: Analogue output 0...10 V
Electrical connection
−M12 : M12 5−pin plug
Fig.2
2
M
etho
d
o
f
oper
a
tion
a
n
d
us
e
The SFE1−LF−... has been designed for monitoring the changes in flow and con
sumption in pipeline systems or terminal equipment in industry. Measurement is
carried out by means of a thermal procedure. The amount of heat, which is drawn
from a heated surface of the sensor by the medium flowing through it, is calcu
lated here. The flow rate or the accumulated consumption of the amount of heat
drawn is calculated and shown on the display. Connection to higher−order systems
is made via 2 digital outputs (Out A/B) and an analogue output Out C). Switching
points can be defined for both digital outputs. For measuring the flow, switching
points are possible for both digital outputs; for the accumulated consumption
measurement a switching pulse for output A (Out A). The combination of accumu
lated consumption measurement (Out A) and flow measurement (Out B) is pos
sible. The flow rate value is passed on via the analogue output.
Ple
as
e note
The product is suitable exclusively for industrial purposes. It is not suitable for
calculting purposes in business, e.g. for calculating consumption in supply
equipment.
Summary of Contents for SFE1-LF F10 Series
Page 28: ...SFE1 LF Festo SFE1 LF 0503NH Deutsch 28 1 1 Grundzustand RUN Modus Bild 22 SHOW Modus ...
Page 30: ...SFE1 LF Festo SFE1 LF 0503NH Deutsch 30 ...
Page 56: ...SFE1 LF Festo SFE1 LF 0503NH English 56 1 1 Basic status RUN mode Fig 22 SHOW mode ...
Page 58: ...SFE1 LF Festo SFE1 LF 0503NH English 58 ...
Page 59: ...SFE1 LF Festo SFE1 LF 0503NH 59 de Lochbilder en Hole pattern ...