Festo SFAM-62 Operating Instructions Manual Download Page 7

1.

Before  teaching  in  EDIT  mode,  select  the  desired  switching  function
(threshold  value  or  window  comparator) 

è

chapter5.4.  EDIT  mode.

Threshold  comparator

Window  comparator

The  (taught)  switching  point  is  derived  from  the
average  value  of  both  measurement  values
SP  =  1/2  (Flow1  +  Flow2)
Special  case:  SP  =  Flow1  =  Flow2

The  taught  switching  window  is  derived  from
the  measurement  values:
SP.Lo  =  Flow1
SP.Hi  =  Flow2

Fig.17

For  teaching  the  switching  variables:
2.

Generate  a  flow  (Flow1)

3.

First  press  the  A  button  and  then  also  the  Edit  button.
[OutA]  and  bar  display  flash  and  the  measurement  value  is  taken  over  as  the
first  Teach  point  or  [Lock]  flashes  if  security  blocking  is  active.

Only  with  active  security  blocking  [Lock]  (points  4  and  5):
4.

Press  the  A/B  buttons  until  the  chosen  security  code  is  set.

5.

Press  the  Edit  button.
[OutA]  and  the  bar  display  flash  and  the  measurement  value  is  taken  over  as
the  first  Teach  point.

6.

Generate  a  second  flow  (Flow2)

7.

First  press  the  A  button  and  then  also  the  Edit  button.
The  second  Teach  point  is  taken  over  and  the  switching  point  (SP)  or
switching  points  (SP.Lo  and  SP.Hi)  become  valid.
The  SFAM  is  in  RUN  mode.

5.6 RECORDER  mode

Fig.18

In  the  RECORDER  mode,  a  manual  accumulated  air  consumption  measurement  can
be  performed.
1.

Press  the  A  button  and  B  button  at  the  same  time.
The  status  of  the  air  consumption  measurement  [Run]  or  [Stop]  is  displayed.

2.

If  [Stop]  is  displayed,  press  the  A  button.
[Run]  with  a  running  light  is  displayed.  The  air  consumption  measurement  is
started.

3.

Press  the  A  button  again.
[Stop]  is  displayed.  The  air  consumption  measurement  is  stopped.

4.

Press  the  A  button  and  B  button  at  the  same  time.
The  SFAM  is  in  RUN  mode.

Note

If  the  RECORDER  mode  is  left  during  an  ongoing  air  consumption  measurement
[Run],  the  air  consumption  measurement  will  continue  in  the  background.

Resetting  measurement  value  to  zero.

· Press  the  B  button  in  the  RECORDER  mode  to  reset  a  measurement  value  to

zero.

6

Operation

Important

Excessive  internal  heat  will  destroy  the  SFAM.
· Avoid  high  cycle  frequencies  with  large  pressure  amplitudes.  Otherwise,  the

admissible  limit  temperatures  of  the  used  materials  will  be  exceeded.

The  air  mass  flow  displayed  by  the  SFAM  refers  to  the  standard  conditions  that
were  set  under  Options  in  the  special  menu.
When  comparing  volume  flows:
· Make  sure  that  the  volume  flows  to  be  compared  (e.g.operating  volume  flow,

amount  supplied  by  a  compressor,  measured  values  of  a  flow  sensor  from
another  manufacturer)  refer  to  the  same  basic  conditions.

· After  the  power  supply  is  switched  on,  the  SFAM  needs  a  warm−up  time  of

5minutes  until  it  achieves  the  specified  accuracy.

6.1 Resetting  the  SFAM  to  the  factory  settings

(also  if  the  security  code  cannot  be  found)

Note

By  resetting  to  factory  setting,  the  current  settings  are  lost.  If  needed,  note  down
these  settings  before  resetting.

To  reset  the  SFAM  to  factory  setting,  proceed  as  follows:
1.

switch  off  the  operating  voltage

2.

Press  all  three  setting  elements  (A  button  +  B  button  +  Edit  button)
simultaneously  and  hold  them  down.

3.

Switch  the  operating  voltage  back  on.
The  SFAM  is  in  RUN  mode.

7

Care  and  maintenance

· Switch  off  the  following  sources  of  energy  before  cleaning  the  exterior  of  the

device:
 the  operating  voltage
 compressed  air  supply.

· If  necessary,  clean  the  SFAM  from  outside.

Permitted  cleaning  agents  are  soap  suds  (max.  +60°C),  petroleum  ether  and  all
non−abrasive  agents.

8

Dismantling

1.

Switch  off  the  following  sources  of  energy  before  dismantling:
 operating  voltage
 the  compressed  air  supply.

2.

Disconnect  the  respective  connections  from  the  SFAM.

9

Eliminating  malfunctions

Malfunction

Possible  cause

Remedy

Incorrect  measurement
display

SFAM  operated  with
non−permitted  medium

Operate  SFAM  only  with
permitted  media

display

SFAM  contaminated

Replace  device

With  flow  measurement:
Measured  value  is
displayed  flashing

Measurement  outside  permitted
measuring  range

Accuracy  refers  only  to  the
permitted  measuring  range

With  air  consumption
measurement:
Measured  value  is
displayed  flashing

Measuring  range  end  value  is
exceeded  at  least  once.
Specified  accuracy  cannot
therefore  be  maintained.

Make  sure  that  the  measuring
range  end  value  is  not  exceeded.

Outputs  do  not  switch
according  to  the  setting.

Short  circuit/overload  at
relevant  output

Eliminate  short  circuit/overload

Settings  cannot  be  edited
(Lock)

Access  protection  active

Enter  the  security  code

O.FLO

Measurement  range  exceeded
(isdisplayed  in  the  RUN  mode)

Check  operating  conditions

Er1,  Er2,  Er4

Device  defective.

Replace  device

Er9

Measurement  range  fallen  below
(is  displayed  in  the  RUN  mode)

Check  operating  conditions

Er10

Measurement  range  exceeded
(isdisplayed  in  the  RUN  mode)

Check  operating  conditions

Er17

Undervoltage

Maintain  operating  voltage

g

Check  electrical  wiring

Fig.19

10

Accessories

Select  the  appropriate  accessories  from  our  catalogue.

è

www.festo.com/catalogue/SFAM

Summary of Contents for SFAM-62

Page 1: ...tion SFAM T or combination with service units of the MS series SFAM M Measurement is carried out by means of a thermal procedure The amount of heat which is drawn from a heated surface of the sensor b...

Page 2: ...ed to the connection where the sieve cartridge on type SFAM M or the starting stretch on type SFAM T is situated The air mass flow is taken from the opposite connection In order to maintain the accura...

Page 3: ...pressing Edit button for 3 seconds or passage of a monitoring time timeout 1 Switch on the operating voltage The SFAM is in RUN mode 2 Check the settings of the SFAM chapter 5 3 SHOW mode 5 1 Symbols...

Page 4: ...e CI switching element function no nc closer opener minimum flow value F Lo Flow Low In order to delete the minimum value press the EDIT button briefly maximum flow value F Hi Flow High In order to de...

Page 5: ...Hy flashes 8 Set the value for the hysteresis Hy with the A B buttons 9 Press the Edit button to confirm the set value no or nc flashes 10 Select the switching element function no nc with the A B but...

Page 6: ...oothing to d6 maximum smoothing With increasing smoothing the switch on switch off time of the switch outputs rises With d OFF the response time of the analogue output equals the set response time Sig...

Page 7: ...be compared e g operating volume flow amount supplied by a compressor measured values of a flow sensor from another manufacturer refer to the same basic conditions After the power supply is switched...

Page 8: ...Electronics Operating voltage range DC V 15 30 Protection against polarity reversal For all electrical connections Electromechanics Electrical connection Straight plug M12x1 5 pin Max length of connec...

Reviews: