Festo SFAM-62 Operating Instructions Manual Download Page 6

a) Setting  standard  conditions
The  air  mass  flow  measured  and  output  by  the  SFAM  refers  to  standard  conditions.
The  SFAM  is  calibrated  at  the  factory  to  the  physical  standard  conditions  in
accordance  with  DIN1343  and  the  unit  to  l/min.

Note

If  different  standard  conditions  and/or  other  units  units  in  contrast  to  the
calibrated  measurement  range  using  the  unit  l/min,  then  there  are  appropriate
characteristic  limits 

è

Fig.22  in  the  chapter  11  Technical  specifications.

The  following  standard  conditions  can  be  selected  under  the  point  [Option].

Option

Off

1

2

Standard  litres  as  per

DIN  1343

ISO  2533

ISO  6358

Air  pressure  (absolute)

[bar]

1.01325

1.01325

1

Temperature

[°C]

0

15

20

Fig.14

3.

Select  the  desired  setting  (OFF,  1  or  2)  with  the  A/B  buttons.

4.

Press  the  Edit  button  to  confirm  the  selection.
[FLW]  is  displayed  and  the  currently  chosen  value  flashes.
The  unit  for  the  flow  (l/min  or  scfm)  can  be  set.

b) Setting  the  physical  unit  for  the  flow
5.

Select  the  desired  setting  (l/min  or  scfm)  with  the  A/B  buttons.

6.

Press  the  Edit  button  to  confirm  the  selection.
[AnA.F]  with  the  currently  set  value  is  displayed. 
The  analogue  filter  can  be  set.

Note

The  configured  physical  unit  is  shown  in  the  RUN  mode  in  the  display  at  the
bottom  right.

c) Setting  filter  time  constants  for  the  analogue  filter
With  the  analogue  filter,  the  rise  time  (filter  time  constants)  of  the  analogue  output
can  be  changed  (default  value  =  60ms).
7.

Choose  the  value  for  the  filter  time  constants  (15ms,  30ms,  60ms,  125ms,
250ms,  500ms  or  999ms)  with  the  A/B  buttons.

8.

Press  the  Edit  button  to  confirm  the  set  value.
[dIG.F]  with  the  currently  chosen  value  flashes.  The  digital  filter  can  be  set.

d) Setting  smoothing  for  the  digital  filter
The  display  values  can  be  smoothed  with  the  digital  filter.  The  degree  of  smoothing
can  be  set  in  6  steps  from  d1=lowsmoothing  to  d6=maximumsmoothing.  With
increasing  smoothing,  the  switch−on  /  switch−off  time  of  the  switch  outputs  rises.
With  d.OFF,  the  response  time  of  the  analogue  output  equals  the  set  response
time.

Signal  flow  from  the  analogue  filter  and  digital  filter

Sensor

Raw  signals

Analogue  filter

Digital  filter

Display

Switching

outputs

Out  A/Out  B

Analogue  output

Fig.15

Note

A  high  filter  time  constant  and  high  smoothing  can  result  in  a  response  time  of
several  seconds.

9.

Select  the  value  for  dampening  (d1  to  d6  or  d.OFF)  with  the  A/B  buttons.

10. Press  the  Edit  button  to  confirm  the  set  value.

[ConS]  is  displayed  and  the  currently  chosen  value  flashes.
The  unit  for  the  air  consumption  (m

3

,  scf  or  l)  can  be  set.

e) Setting  the  physical  unit  for  the  flow
11. Select  the  desired  setting  (m

3

,  scfm  or  l)  with  the  A/B  buttons.

12. Press  the  Edit  button  to  confirm  the  selection.

The  currently  set  value  [PnP]  or  [nPn]  for  the  switching  element  output
flashes.  The  switching  element  output  can  be  set.

f ) Setting  switching  element  output
The  two  switching  outputs  can  be  set  through  the  integrated  push/pull  stage  as  a
plus  switch  (PNP)  or  zero  switch  (NPN).
13. Select  the  desired  setting  (PNP  or  NPN)  with  the  A/B  buttons.
14. Press  the  Edit  button  to  confirm  the  selection.

[Lock]  flashes.  The  security  code  can  be  set.

g) Setting  security  code
To  protect  the  setting  from  unauthorized  access,  a  numerical  code  of  up  to  4  digits
can  be  set.  The  security  code  must  be  entered  each  time  the  settings  are  changed
(EDIT  mode  and  TEACH  mode).

Note

keep  the  security  code  in  a  safe  place.  If  the  security  code  has  been  forgotten
see  the 

è

chapter6.1  Resetting  SFAM  to  factory  setting.

15. Set  the  desired  security  code  with  the  A/B  buttons.
16. Press  the  Edit  button  to  confirm  the  selection.

The  SFAM  is  in  RUN  mode.

5.5 TEACH  mode

In  TEACH  mode,  the  switching  points  can  be  taught.

Note

The  process  is  the  same  for  teaching  the  switching  outputs  OutA  (A  button)  and
OutB  (B  button).  In  the  following,  the  process  is  described  using  the  switching
output  OutA.

Fig.16

Summary of Contents for SFAM-62

Page 1: ...tion SFAM T or combination with service units of the MS series SFAM M Measurement is carried out by means of a thermal procedure The amount of heat which is drawn from a heated surface of the sensor b...

Page 2: ...ed to the connection where the sieve cartridge on type SFAM M or the starting stretch on type SFAM T is situated The air mass flow is taken from the opposite connection In order to maintain the accura...

Page 3: ...pressing Edit button for 3 seconds or passage of a monitoring time timeout 1 Switch on the operating voltage The SFAM is in RUN mode 2 Check the settings of the SFAM chapter 5 3 SHOW mode 5 1 Symbols...

Page 4: ...e CI switching element function no nc closer opener minimum flow value F Lo Flow Low In order to delete the minimum value press the EDIT button briefly maximum flow value F Hi Flow High In order to de...

Page 5: ...Hy flashes 8 Set the value for the hysteresis Hy with the A B buttons 9 Press the Edit button to confirm the set value no or nc flashes 10 Select the switching element function no nc with the A B but...

Page 6: ...oothing to d6 maximum smoothing With increasing smoothing the switch on switch off time of the switch outputs rises With d OFF the response time of the analogue output equals the set response time Sig...

Page 7: ...be compared e g operating volume flow amount supplied by a compressor measured values of a flow sensor from another manufacturer refer to the same basic conditions After the power supply is switched...