3. Set the switching point (SP or SP.L) with the UP/DOWN button.
4. In order to confirm, press the EDIT button.
With switching function Window Comparator:
[SP.H] is shown briefly. Segment 8 of the bar display flashes.
5. Set the value (SP.H) with the UP/DOWN button.
SP.H lies above SP.L up to the end value in the setting range.
6. In order to confirm, press the EDIT button.
[HY] is shown briefly. 3 segments of the bar display flash.
7. Set the hysteresis (HY) with the UP/DOWN button.
8. In order to confirm, press the EDIT button.
[no] or [nc] flashes.
9. Set the switching characteristic [no/nc] with the UP/DOWN button.
10. In order to confirm, press the EDIT button.
[fil] flashes.
11. Set the time−constant switching point (1 or 5 or 20) with the UP/DOWN button.
12. In order to confirm, press the EDIT button.
The device is then in the RUN mode again.
Please note
Check your set values in the SHOW mode.
Setting the unit o
f
measurement and the security code
The current unit ([%] or [kPA] or [psi] or [bar]) flashes.
1. Use the UP/DOWN button to select the desired unit.
2. In order to confirm, press the EDIT button.
[lock] flashes.
3. Set the desired security code with the UP/DOWN button.
(OFF = no protection).
Summary of Contents for MS-LFM-...-DN Series
Page 25: ...MS LFM DP DN DPI DNI Festo MS LFM DP DN DPI DNI 0611NH Deutsch 25 Bild 16 EDIT Modus...
Page 26: ...MS LFM DP DN DPI DNI Festo MS LFM DP DN DPI DNI 0611NH Deutsch 26 Bild 17 SHOW Modus...
Page 28: ...MS LFM DP DN DPI DNI Festo MS LFM DP DN DPI DNI 0611NH Deutsch 28...
Page 51: ...MS LFM DP DN DPI DNI Festo MS LFM DP DN DPI DNI 0611NH English 51 Fig 16 EDIT mode...
Page 52: ...MS LFM DP DN DPI DNI Festo MS LFM DP DN DPI DNI 0611NH English 52 Fig 17 SHOW mode...
Page 54: ...MS LFM DP DN DPI DNI Festo MS LFM DP DN DPI DNI 0611NH English 54...
Page 55: ...MS LFM DP DN DPI DNI Festo MS LFM DP DN DPI DNI 0611NH 55...