2. Commissioning
2-8
Festo P.BE-CTEU-EC-OP+MAINT-EN en 1208NH
Fig. 2/1:
Example: configuration for a valve terminal and an input module in auto mode
Tool change mode
In tool change mode, only the data width of each I-port is
defined; the specific components that can be connected are
not.
The startup parameters are configured by activating tool
change mode for each I-port and defining the data width. This
ensures that the correct module configuration, i.e. data
width, is requested after each startup. Each I-port is assigned
a fixed I/O data length.
The I/O data lengths are configured via the CoE objects
0x8200 and 0x820A (
section A.4). The I/O data length for
both I-ports must not exceed 16 bytes. If the image table ex-
ceeds the defined I/O data length, the excess bytes will be
excluded. If the modular ESI file is used, the number of bytes
must correspond to the formula 2
n
where n = 0, 1, 2, 3 or 4
(i.e.: 1, 2, 4, 8 or 16 bytes).
The connected I-port devices can be exchanged freely. No
diagnostics messages are generated when devices are re-
placed. Only if the I-port configuration “expect device” is se-
lected is the message
“Output data size is greater than configured” generated when
a device with an I/O length greater than that configured in
tool change mode is connected (
section 2.1.4).
Summary of Contents for CTEU-EC
Page 2: ......
Page 16: ...Contents and general safety instructions XIV Festo P BE CTEU EC OP MAINT EN en 1208NH...
Page 17: ...Installation 1 1 Festo P BE CTEU EC OP MAINT EN en 1208NH Chapter 1 Installation...
Page 34: ...1 Installation 1 18 Festo P BE CTEU EC OP MAINT EN en 1208NH...
Page 35: ...Commissioning 2 1 Festo P BE CTEU EC OP MAINT EN en 1208NH Chapter 2 Commissioning...
Page 60: ...2 Commissioning 2 26 Festo P BE CTEU EC OP MAINT EN en 1208NH...
Page 61: ...Diagnostics 3 1 Festo P BE CTEU EC OP MAINT EN en 1208NH Chapter 3 Diagnostics...
Page 82: ...3 Diagnostics 3 22 Festo P BE CTEU EC OP MAINT EN en 1208NH...
Page 83: ...Technical appendix A 1 Festo P BE CTEU EC OP MAINT EN en 1208NH Appendix A Technical appendix...
Page 103: ...Index B 1 Festo P BE CTEU EC OP MAINT EN en 1208NH Appendix B Index...
Page 104: ...B Index B 2 Festo P BE CTEU EC OP MAINT EN en 1208NH Contents B Index B 1...
Page 109: ...B Index B 7 Festo P BE CTEU EC OP MAINT EN en 1208NH U User instructions X X X1 X2 LEDs 3 6...
Page 110: ...B Index B 8 Festo P BE CTEU EC OP MAINT EN en 1208NH...