Festo CPX-FB11 0206NH English
19
DIL switches
Description
3
3.1, 3.2
Diagnosis via “Polled” or “Change of state”
connection:
3.1
3.2
OFF
OFF: Diagnosis switched off
OFF
ON: I/O diagnostic interface is
switched on
ON
OFF: Status bits are switched on
ON
ON: Reserved for extensions
4
4.1
4.2
4.2
4.1
OFF
OFF: 125 kBaud
OFF
ON: 250 kBaud
ON
OFF: 500 kBaud
ON
ON: Auto
1)
5
5.1
5.2
5.3
5.4
5.5
5.6
Field bus station number binary coded
(0 for OFF, 1 for ON)
5.6
to
5.1
0 0 0 0 0 1 = 1
0 0 0 0 1 0 = 2
0 0 0 0 1 1 = 3
0 0 0 1 0 0 = 4
0 0 0 1 0 1 = 5
etc.; permitted value range: 0...63
1)
Automatic baud rate recognition in the switch-on phase of
the CPX terminal when connected to a bus system which is
running (exchange of data between a scanner and at least
one slave). 125 KBd is set if no baud rate is recognized.