Festo — CPX-F8DE-P — 2022-10d
Commissioning
PROFIsafe
parameters
General description
The following applies for
CPX-F8DE-P:
Value
F_Dest_Add
(PROFIsafe target
address)
Unique PROFIsafe target
address of the F-Device
within the PROFIsafe net-
work. The target address set
by the configuration software
must match the PROFIsafe
address set on the input
module with the DIL switch.
–
CPX-F8DE-P compares
both settings to check the
authenticity of the connec-
tion
–
1 ... 1022
(0 and 1023 are
not permitted)
F_WD_Time
Time (Watchdog Time) within
which a valid current safety
telegram must be received
from the F-Host. Otherwise
the F-Device switches to the
safe state.
–
The watchdog time must
be short enough for
the system to react fast
enough to communication
failures or malfunctions.
On the other hand, the
watchdog time must be
long enough to tolerate
typical delays in transmis-
sion. The cycle time for
calling the safety program
must be shorter than the
watchdog time set here.
–
50 ... 65535 [ms]
F_iPar_CRC
CRC via the individual device
parameters (i-parameters).
–
CPX-F8DE-P does not pro-
vide individual device
parameters.
–
0
(cannot be
changed)
Tab. 27: PROFIsafe parameters
4.7
Reading out the CPX module parameters
Further information on parameterisation can be found in the CPX system description for CPX-SYS-… or
the description of the bus node.
The following table provides an overview of the existing CPX module parameters on the input module.
Overview of module parameters CPX-F8DE-P
Function number
1)
Bit
Module parameters
Default
4828 + m * 64 +1 ... 5
0 ... 7
reserved
–
4828 + m * 64 +8 ... 21
0 ... 7
Reserved for PROFIsafe
–