Festo — CPX-F8DE-P — 2022-10d
Diagnostics and error handling
79
Channel
error LED
FP PED
Module
error LED
Error
no.
Fault description
Remedy
67
The chronological
sequence of the PROFI-
safe communication is
malfunctioning
–
Check communication
paths.
–
Check timeout time
69
Fault in safe parameterisa-
tion (safety parameterisa-
tion invalid)
–
Check parameters in
PROFIsafe program log.
–
Transmit new parame-
ters.
75
Input module overtemper-
ature short circuit/over-
load at a clock output
–
Remedy overtempera-
ture.
–
Remedy short cir-
cuit/overload on T0, T2,
T4, T6.
145
Input module has detected
an error during the self-
test
–
Switch CPX terminal on
again.
–
Replace input module.
Tab. 39: Behaviour in response to module errors
All input channels on the input module are passivated in response to module errors.
–
After remedial action: reintegrate the input module.