Festo CPX-E-CEC EP Series Instructions Manual Download Page 6

Power supply

Operating power supply
U

EL/SEN

[V DC]

24 

_

 25%

Intrinsic current consumption
at nominal operating voltage
24 V from U

EL/SEN

[mA]

Typ. 150

Reverse polarity protection
24 V U

EL/SEN

 against

0 V U

EL/SEN

Yes

Mains buffering time

[ms]

20

Tab. 19 Power Supply

Network-specific data

Protocol

EtherNet/IP

1)

, EtherCAT

Transmission rate

[Mbps]

10/100 (full duplex/half duplex)

Crossover detection

Auto-MDI/MDI-X

Maximum cable length per
segment

[m]

100

2)

Cable specification

Cable type

Ethernet twisted pair cable, shielded

Transmission class

Category Cat 5/Cat 5e (link class)

Cable diameter

[mm]

6 … 8

Wire cross section

[mm

2

]

0.14 … …0.75; 22 AWG

3)

1) based on the Ethernet protocol IEEE 802.3
2) at a transmission rate of 100 Mbps
3) required for maximum connection length between network participants

Tab. 20 Network-specific Data

13.2

Technical Data UL/CSA Certification

Ambient conditions UL/CSA

Pollution degree

3

Installation site

for indoor use only

Max. installation height

[m]

2000

Tab. 21 Ambient Conditions UL/CSA

Ambient temperature

Mounting position

Vertical

Horizontal

Operating power supply U

EL/SEN

 via XD

Ambient temperature, max. current rating
of terminal strip 

£

 4 A

[°C]

–5 … +60

–5 … +50

Ambient temperature, max. current rating
of terminal strip 

>

 4 … 8 A

[°C]

–5 … +50

–5 … +40

Operating voltage U

EL/SEN

 with feed via both connections [XD]

1)

Ambient temperature, max. current rating
of terminal strip 

>

 4 … 8 A

[°C]

–5 … +60

–5 … +50

1) see chapter 'Product design' or 'Connection elements'

Tab. 22 Ambient temperature ranges