Switch status

Function

Run (standard setting)

A project can be started using CODESYS (run mode active).
A CODESYS boot application can be started.

Stop

A project cannot be started using CODESYS.
A CODESYS boot application cannot be started.

Run 

è

 Stop

A project that is running will be stopped.

Stop 

è

 Run

A project that was stopped using the run/stop switch will be contin-
ued.

Tab. 5 Run/stop switch

5.2.3.2

Rotary switch

NOTICE!

Damage to internal electronics.

Damage to at-risk components due to electrostatic discharge.

Ensure your body is electrostatically discharged before activating the rotary
switch.

Activate rotary switch as required.

Rotary switch

Function

The 3 rotary switches are used to set the 4th octet of the IP address
for the EtherNet/IP network connection: 192.168.1.XXX.

Possible settings

0 = use the internal configuration (factory setting)
1 … 254 = Permissible address range
999 = reset to factory setting
For invalid values, the internal configuration is used.

Factory setting

192.168.1.1 (DHCP active)

The DIL switches are reserved and have no function.

Tab. 6 Rotary switch

Changes to the rotary switches only take effect following a restart of the module.

5.2.3.3

Operator unit CDSB (optional)

The operator unit CDSB is available as an accessory

è

 www.festo.com/catalogue.

The functions of the operator unit are described in the “Description of controller
CPX-E-CEC-...-EP” 

è

 1.1 Further applicable documents.

5.2.4

Connecting components

5.2.4.1

Operating voltage supply

Port [XD]

1)

Signal

0

1

+24 V DC operating voltage supply U

EL/SEN

2

3

0 V DC operating voltage supply U

EL/SEN

1) The ports XD.0 and XD.1 and also XD.2 and XD.3, respectively, are interconnected in the terminal strip.

Tab. 7 Port [XD]

5.2.4.2

Network connections

Port [XF1], [XF2], [ETH1], [ETH2],
[EC]

Signal

1

TD+

Transmitted data +

2

TD–

Transmitted data –

3

RD+

Received data +

4

n.c.

5

n.c.

6

RD–

Received data –

7

n.c.

8

n.c.

1)

Shield

Functional earth

1) Housing

Tab. 8 Port [XF1], [XF2], [ETH1], [ETH2], [EC]

Connection

Function

[XF1]

EtherNet/IP Port 1

[XF2]

EtherNet/IP Port 2

[ETH1]

[ETH2]

Ethernet interfaces for the connection of a programming device,
PC or operating unit CDPX

[EC]

EtherCAT Master

Tab. 9 Network connections

The network connections ETH1 and ETH2 are connected to the controller via a
switch.

5.2.4.3

Memory card slot [Card]

The slot is used to save data and results to a memory card CAMC-M-MS-G32.

The data are saved in the directory /mnt/sdcard.

The data are accessed through SysFile and CAA.File 

è

 CODESYS libraries.

Requirements:

Maximum memory size: 32 GB

Formatting: FAT32 (one partition only)

When using a memory card, please note the direction and orientation.

Use only memory cards that are sold by Festo as accessories for the product

è

 www.festo.com/catalogue.

Festo does not provide any warranty for the use of other memory cards.

The memory card slot is only intended for user-monitored operation.

Do not use memory cards for continuous data recording.

Memory cards cannot be used to execute CODESYS boot projects.

5.2.4.4

USB interface [USB]

The USB interface (A-coded socket, USB specification 2.0) is used to save data
and results to external storage media.

The data from the USB memory are saved in the directory /mnt/usb.

The data are accessed through SysFile and CAA.File 

è

 CODESYS libraries.

Requirements:

Maximum memory size: 32 GB

Formatting: FAT32 (one partition only)

NOTICE!

Impermissible operating states of the controller result from high current con-
sumption at the USB interface.

Use only storage media with a current consumption of 

£

 0.5 A.

The USB interface is only intended for user-monitored operation.

Do not use storage media for continuous data recording.

USB storage devices cannot be used to execute CODESYS boot projects.

6

Transport and storage

Observe specifications for environmental and storage conditions

è

 13 Technical Data

è

 Tab. 21 Ambient Conditions UL/CSA.

7

Assembly

Assemble the module as outlined in the “Instruction manual for Automation
system CPX-E” 

è

 1.1 Further applicable documents.

8

Installation

8.1

Network

NOTICE!

Unauthorised Access to the Device Can Cause Damage or Malfunction.

When connecting the device to a network, protect the network from unauthor-
ised access.
Standards for security in information technology can be used for network pro-
tection measures, e.g. IEC 62443, ISO/IEC 27001.

Network

An access password only protects against unintentional modification.

NOTICE!

Transmission errors due to faulty installation or excessive transmission rates.

Please note the line specifications in the documentation of the controller.