![Festo CPX-E-CEC EP Series Instructions Manual Download Page 3](http://html1.mh-extra.com/html/festo/cpx-e-cec-ep-series/cpx-e-cec-ep-series_instructions-manual_2283165003.webp)
Switch status
Function
Run (standard setting)
A project can be started using CODESYS (run mode active).
A CODESYS boot application can be started.
Stop
A project cannot be started using CODESYS.
A CODESYS boot application cannot be started.
Run
è
Stop
A project that is running will be stopped.
Stop
è
Run
A project that was stopped using the run/stop switch will be contin-
ued.
Tab. 5 Run/stop switch
5.2.3.2
Rotary switch
NOTICE!
Damage to internal electronics.
Damage to at-risk components due to electrostatic discharge.
•
Ensure your body is electrostatically discharged before activating the rotary
switch.
•
Activate rotary switch as required.
Rotary switch
Function
The 3 rotary switches are used to set the 4th octet of the IP address
for the EtherNet/IP network connection: 192.168.1.XXX.
Possible settings
0 = use the internal configuration (factory setting)
1 … 254 = Permissible address range
999 = reset to factory setting
For invalid values, the internal configuration is used.
Factory setting
192.168.1.1 (DHCP active)
The DIL switches are reserved and have no function.
Tab. 6 Rotary switch
Changes to the rotary switches only take effect following a restart of the module.
5.2.3.3
Operator unit CDSB (optional)
The operator unit CDSB is available as an accessory
è
The functions of the operator unit are described in the “Description of controller
CPX-E-CEC-...-EP”
è
1.1 Further applicable documents.
5.2.4
Connecting components
5.2.4.1
Operating voltage supply
Port [XD]
1)
Signal
0
1
+24 V DC operating voltage supply U
EL/SEN
2
3
0 V DC operating voltage supply U
EL/SEN
1) The ports XD.0 and XD.1 and also XD.2 and XD.3, respectively, are interconnected in the terminal strip.
Tab. 7 Port [XD]
5.2.4.2
Network connections
Port [XF1], [XF2], [ETH1], [ETH2],
[EC]
Signal
1
TD+
Transmitted data +
2
TD–
Transmitted data –
3
RD+
Received data +
4
n.c.
–
5
n.c.
–
6
RD–
Received data –
7
n.c.
–
8
n.c.
–
1)
Shield
Functional earth
1) Housing
Tab. 8 Port [XF1], [XF2], [ETH1], [ETH2], [EC]
Connection
Function
[XF1]
EtherNet/IP Port 1
[XF2]
EtherNet/IP Port 2
[ETH1]
[ETH2]
Ethernet interfaces for the connection of a programming device,
PC or operating unit CDPX
[EC]
EtherCAT Master
Tab. 9 Network connections
The network connections ETH1 and ETH2 are connected to the controller via a
switch.
5.2.4.3
Memory card slot [Card]
The slot is used to save data and results to a memory card CAMC-M-MS-G32.
–
The data are saved in the directory /mnt/sdcard.
–
The data are accessed through SysFile and CAA.File
è
CODESYS libraries.
Requirements:
–
Maximum memory size: 32 GB
–
Formatting: FAT32 (one partition only)
When using a memory card, please note the direction and orientation.
Use only memory cards that are sold by Festo as accessories for the product
è
Festo does not provide any warranty for the use of other memory cards.
The memory card slot is only intended for user-monitored operation.
•
Do not use memory cards for continuous data recording.
Memory cards cannot be used to execute CODESYS boot projects.
5.2.4.4
USB interface [USB]
The USB interface (A-coded socket, USB specification 2.0) is used to save data
and results to external storage media.
–
The data from the USB memory are saved in the directory /mnt/usb.
–
The data are accessed through SysFile and CAA.File
è
CODESYS libraries.
Requirements:
–
Maximum memory size: 32 GB
–
Formatting: FAT32 (one partition only)
NOTICE!
Impermissible operating states of the controller result from high current con-
sumption at the USB interface.
•
Use only storage media with a current consumption of
£
0.5 A.
The USB interface is only intended for user-monitored operation.
•
Do not use storage media for continuous data recording.
USB storage devices cannot be used to execute CODESYS boot projects.
6
Transport and storage
•
Observe specifications for environmental and storage conditions
è
Tab. 21 Ambient Conditions UL/CSA.
7
Assembly
•
Assemble the module as outlined in the “Instruction manual for Automation
system CPX-E”
è
1.1 Further applicable documents.
8
Installation
8.1
Network
NOTICE!
Unauthorised Access to the Device Can Cause Damage or Malfunction.
•
When connecting the device to a network, protect the network from unauthor-
ised access.
Standards for security in information technology can be used for network pro-
tection measures, e.g. IEC 62443, ISO/IEC 27001.
Network
An access password only protects against unintentional modification.
NOTICE!
Transmission errors due to faulty installation or excessive transmission rates.
•
Please note the line specifications in the documentation of the controller.